D - 24
Appendix D
•
Vission 20/20 Communication Table
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Vilter
TM
Address
Ethernet
IP
Address
Modbus
Address
Command Name
Data
Type
Value
Mode
Lower
Range
Higher
Range
437
N69:1
41171
Profile
ENUM
"0 = Summer
1 = Winter"
Read-Write
438
N69:2
41172
High to Low Speed Fan
Delay (seconds)
INT
Read-Write 5
30
439
N69:3
41173
Condenser Setpoint
F-INT
Read-Write 100.0
150.0
440
N69:4
41174
Upper Deadband
F-INT
Read-Write 0.5
20.0
441
N69:5
41175
Lower Deadband
F-INT
Read-Write 0.5
20.0
442
N69:6
41176
Wetbulb Offset
F-INT
Read-Write 0.5
20.0
443
N69:7
41177
Switch Temp
F-INT
Read-Write 25.0
45.0
444
N69:8
41178
Summer/Winter Auto
Switch Enabled
INT
0 = Disabled, 1 = Enabled
Read-Write
445
N69:9
41179
Wetbulb Override
Enabled
INT
0 = Disabled, 1 = Enabled
Read-Write
446
N69:10
41180
Step #1 Enabled
(Summer, Winter)
INT
0 = Disabled, 1 = Enabled
Read-Write
447
N69:11
41181
Step #2 Enabled
(Summer, Winter)
INT
0 = Disabled, 1 = Enabled
Read-Write
448
N69:12
41182
Step #3 Enabled
(Summer, Winter)
INT
0 = Disabled, 1 = Enabled
Read-Write
449
N69:13
41183
Step #4 Enabled
(Summer, Winter)
INT
0 = Disabled, 1 = Enabled
Read-Write
450
N69:14
41184
Step #5 Enabled
(Summer, Winter)
INT
0 = Disabled, 1 = Enabled
Read-Write
451
N69:15
41185
Step #1 Out#1 Enabled
(Summer, Winter)
INT
0 = Disabled, 1 = Enabled
Read-Write
452
N69:16
41186
Step #2 Out#1 Enabled
(Summer, Winter)
INT
0 = Disabled, 1 = Enabled
Read-Write
453
N69:17
41187
Step #3 Out#1 Enabled
(Summer, Winter)
INT
0 = Disabled, 1 = Enabled
Read-Write
454
N69:18
41188
Step #4 Out#1 Enabled
(Summer, Winter)
INT
0 = Disabled, 1 = Enabled
Read-Write
455
N69:19
41189
Step #5 Out#1 Enabled
(Summer, Winter)
INT
0 = Disabled, 1 = Enabled
Read-Write
456
N69:20
41190
Step #1 Out#2 Enabled
(Summer, Winter)
INT
0 = Disabled, 1 = Enabled
Read-Write
457
N69:21
41191
Step #2 Out#2 Enabled
(Summer, Winter)
INT
0 = Disabled, 1 = Enabled
Read-Write
458
N69:22
41192
Step #3 Out#2 Enabled
(Summer, Winter)
INT
0 = Disabled, 1 = Enabled
Read-Write
459
N69:23
41193
Step #4 Out#2 Enabled
(Summer, Winter)
INT
0 = Disabled, 1 = Enabled
Read-Write
460
N69:24
41194
Step #5 Out#2 Enabled
(Summer, Winter)
INT
0 = Disabled, 1 = Enabled
Read-Write
461
N69:25
41195
Step #1 Out#3 Enabled
(Summer, Winter)
INT
0 = Disabled, 1 = Enabled
Read-Write
462
N69:26
41196
Step #2 Out#3 Enabled
(Summer, Winter)
INT
0 = Disabled, 1 = Enabled
Read-Write
Содержание Vilter Vission 20/20
Страница 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Страница 2: ......
Страница 4: ......
Страница 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Страница 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Страница 336: ......
Страница 337: ......