10 – 3
Section 10
•
Compressor Sequencing
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Table 10-1. Status Symbols
Symbol
Description
Default, If slave Compressor is not present.
Slave Compressor is configured in sequencing table
but is not configured in “Remote” mode or is not de
-
tected in network.
Slave Compressor configured in sequencing table
and is in ready to run state.
Slave Compressor is running with Alarm condition.
Slave Compressor stopped due to Error Condition.
Slave Compressor running at maximum capacity
without any error.
Slave Compressor under active control of Master
Compressor
Slave Compressor running into its stop timer, will be
stopped.
Slave Compressor is next in sequence for unloading.
Slave Compressor running into its start timer, will be
started.
Status Symbols
Compressor sequencing status symbols are automati-
cally refreshed every 10 seconds. For symbols, see
Table 10-1.
NOTE
Before configuring the Sequencing table on the
Master Compressor, log on to the slave compressors
one by one and enable sequencing in slave mode,
and put each slave in Remote mode. Then log on to
Master Compressor and wait till all slaves show up
under detected devices pop-up screen. Add slaves,
which in turn will get shown in Devices List Screen
and also in Equipment combo-box.
Содержание Vilter Vission 20/20
Страница 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Страница 2: ......
Страница 4: ......
Страница 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Страница 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Страница 336: ......
Страница 337: ......