14 – 3
Section 14
•
Slide Calibration
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Calibrate Slide Valve Actuators
Assuming that the actuator’s motors have not been
calibrated, the transmitter output of the actuator motor
will fluctuate wildly until they are calibrated. To prevent
damage to actuator’s motors, do not connect the Power
Cable (Yellow TURCK cable) or the Position Transmitter
Cable (Gray TURCK cable) until instructed to do so in this
procedure.
1. Open the plastic cover of the capacity motor by
removing four screws. Gently lift the cover and tilt
it toward the TURCK connectors. Raise the cover
enough to be able to press the blue calibrate but-
ton and to be able to see the red LED on the top of
the assembly, see Figure 14-2.
2. Log into the Vission 20/20.
3. From the main screen select the Menu button, and
then the Slide Calibration button, see Figure 14-3.
4. When the “Slide Calibration” screen appears, then
you can safely connect the Power Cable (Yellow
TURCK cable) and the Position Transmitter Cable
(Gray TURCK cable) to the Capacity motor.
5. Press “+” or “-” to move the slide valves to check
the rotation, see Table 14-1 for proper shaft rota-
tion. If for any reason the “+” or “-” command on
the panel does not correspond to the slide increase
or decrease, swap the blue & brown wires of the
Yellow TURCK cable in the control panel to reverse
the rotation of the motor.
6. Quickly press and release the BLUE CALIBRATION
BUTTON on the ACTUATOR motor once, see Figure
14-4. This instructs the ACTUATOR motor to enter
the calibration mode. The red LED on the actuator
control board will begin flashing. Use the “-” but
-
ton on the Vission 20/20 panel to drive the capacity
slide to its minimum mechanical stop position.
This will be apparent by a slowing of the motor rota-
tion and a winding sound from the actuator motor.
When you hear the motor wind-up, release the “-”
button.
Then use the “+” button to pulse the motor so that
the capacity slide is “just off” of its minimum posi-
tion and there is no tension on the motor shaft.
7. Quickly press and release the BLUE CALIBRATION
BUTTON on the ACTUATOR motor once. The red
LED will now flash at a slower rate. This now in
-
structs the ACTUATOR motor that this point is the
minimum slide position. This point will correspond
to 0 volts AFTER the ACTUATOR calibration proce-
dure is completed.
Figure 14-2. Actuator Assembly
Blue
Calibrate
Button
Red LED
Actuator
Plastic Cover
Actuator
Assembly
View Rotate 180°
CAUTION
DO NOT CONTINUE TO ENERGIZE THE ACTUATOR
MOTOR AFTER THE SLIDE HAS REACHED THE
MECHANICAL STOP. Doing so may cause mechanical
damage to the motor or shear the motor shaft key.
When the slide has reached the mechanical stop po-
sition, press the button in the center of the photo-
chopper to release the brake, and thereby release the
tension on the actuator motor.
Содержание Vilter Vission 20/20
Страница 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Страница 2: ......
Страница 4: ......
Страница 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Страница 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Страница 336: ......
Страница 337: ......