25 – 1
Section 25
•
Cool Compression Control
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Overview
The cool compression operation is similar to the one
of the standard single screw compressor units, except
there is no external oil cooler to the unit. A blanket of
liquid ammonia lies on top of the oil in the oil separa-
tor. The liquid ammonia level is regulated by sensing
the liquid ammonia level with a level probe, and using
a positioning valve to vary the amount of liquid ammo-
nia being added to the separator. The cooling occurs
through the entire compression and separation process.
The Cool Compression compressor does not have an oil
pump. When the Cool Compression compressor unit is
commanded to start, the control panel first insures that
the slide valves are at their minimum positions. The suc-
tion oil injection solenoid (SOI) is energized – allowing a
path for oil to flow into the compressor. The compressor
now starts. There is an initial pressure drop in the suc-
tion chamber of the compressor and a corresponding
increase in pressure on the discharge of the compres-
sor. This creates a pressure differential that forces the
oil and liquid ammonia mixture through the suction oil
injection line into the suction chamber of the compres-
sor. This oil and liquid provides lubrication and cooling
until full pressure differential lubrication is attained. As
the differential pressure increases, the oil and liquid am-
monia is now injected into the screw during the com-
pression process and the oil injection valve is allowed to
close.
Setup
Configuration Screen:
• To setup the Vission 20/20 panel for Cool
Compression, first ensure that an analog output
card is installed in the panel, and it is selected from
page 6 of the configuration screen, see Section
19. Navigate to configuration page 2, and select
“Cool Compression” checkbox from the Special
Compressor Settings Section, see Figure 25-1. Once
selected, the “Cool Compression” option will appear
Figure 25-1. Configuration Screen
Содержание Vilter Vission 20/20
Страница 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Страница 2: ......
Страница 4: ......
Страница 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Страница 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Страница 336: ......
Страница 337: ......