10 – 17
Section 10
•
Compressor Sequencing
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Figure 10-15. Compressor Setup for Compressor Sequencing Master
SETTING UP THE MASTER COMPRESSOR
NOTE
The master compressor will ALWAYS be the
highest priority compressor – and act as the trim
compressor. So this must be taken into account
when deciding which compressor is to act as the
master compressor.
Log onto the master compressor and navigate to the
Configuration screen, see Figure 10-15.
1. Enable the Ethernet port and select the Modbus
TCP protocol.
2. Setup a unique Ethernet IP address for the master.
3. Setup the Subnet Mask for the IP address.
4. Setup the Gateway address. (MUST DO!)
5. Enable the Compressor Sequencing check box and
select “Master”.
6. Select a Network Name for the master compressor.
(Network Name must be same for Master & Slave
Compressors)
7. Select a Unique Name for the master compressor.
8. Set the Communications Active Remote Control to
“ETHERNET”.
9. Apply these settings before exiting the
Configuration screen.
At this point, the master will begin receiving the slave
compressors information from the network and will
populate it in the View Detected Devices pop-up of the
Compressor Sequencing screen. If after a couple of min-
utes you do not see the slave compressors listed under
the View Detected Devices list, then power cycle the
master compressor panel.
Содержание Vilter Vission 20/20
Страница 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Страница 2: ......
Страница 4: ......
Страница 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Страница 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Страница 336: ......
Страница 337: ......