C - 25
Appendix C
•
Remote Control and Monitoring of Vission 20/20 Panel
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
within the Modbus range of 40500 through 40513
can occur. If Remote Lock is ON, then writes within
this region cannot occur. These registers are the
compressor control registers (Start, Stop, Caphold
etc). Remote Lock is typically used to lock out a PLC
or central computer while the operator is operating
the compressor locally. The Remote Lock button is
located directly below the Compressor STOP button.
The status of Remote Lock is shown in the upper left
corner of the Main Screen.
RESTART ON POWER FAILURE
• The Vission 20/20 allows for selection of different op-
erations to occur after a power failure has occurred.
The selections determine in which mode of operation
the 20/20 will be placed after the power is restored to
the panel. This should decided upon and setup prior
to communicating to the 20/20 panel.
1. Always
2. Never
3. Timed
4. Remote Lock Off
5. Boot in Remote (Direct I/O)
1. Always
• If the compressor was off prior to the power failure, it
will stay off after the power is restored.
• If the compressor was running prior to the power fail-
ure, it will begin an Auto-restart sequence as soon as
power is restored.
• In both cases, the Remote Lock will be ON after
power is restored, which means it will not accept any
“writes” via communication within the Compressor
Command register region, until someone walks up to
the panel and presses Unit Start-> Remote.
2. Never
• The compressor will not restart after power is re-
stored. The Remote Lock will be ON after power is re-
stored, which means it will not accept any “writes” via
communication within the Compressor Command
register region, until someone walks up to the panel
and presses Unit Start-> Remote.
3. Timed
• The compressor WILL attempt a restart after power is
restored and the Max Restart After Power Failure tim-
er has timed out. The Remote Lock will be ON after
power is restored, which means it will not accept any
“writes” via communication within the Compressor
Command register region, until someone walks up to
the panel and presses Unit Start-> Remote.
4. Remote Lock Off
• The Vission 20/20 panel will boot up with the Remote
Lock OFF which will allow the panel to accept all re-
mote control commands, via communication, imme-
diately after power is restored to the panel.
5. Boot in Remote (Direct I/O)
• The Vission 20/20 panel will boot up with the Remote
Lock OFF and be placed into REMOTE mode, which
will allow the panel to accept Direct I/O commands
immediately after power is restored to the panel.
COMMON REGISTER SETUP TO CONTROL THE
VISSION 20/20 (COMPRESSOR CONTROL) VIA
COMMUNICATIONS
Register Setup and Control Scenario
•
The Vission 20/20 panel first needs to be placed in
REMOTE mode before the Compressor Control com-
mands (Registers 40500 through 40513) can be sent.
To do this, press the green UNIT START button, then
REMOTE.
Modbus Register 40501 - Active Remote Control
Reading this register can be used to verify the Active
Remote Control mode, which was previously setup from
the Configuration screen. Writing to this register can
change the Active Remote Control mode, however this
is not common.
• 0 = None (internal local setpoints will be used to con-
trol the compressor).
• 1 = Direct I/O (hardwired control - via digital inputs.
Refer to wiring diagram.)
• 2 = Serial (serial communications via RS485 Modbus
RTU ).
• 3 = Ethernet (Modbus TCP or Ethernet IP
communications.)
Содержание Vilter Vission 20/20
Страница 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Страница 2: ......
Страница 4: ......
Страница 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Страница 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Страница 336: ......
Страница 337: ......