19 – 9
Section 19
•
Configuration
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Figure 19-4. Configuration Screen - Compressor Control (Page 2)
(Special Compressor Settings)
pumpdown control operation is not running and oil
injection temperature is above the oil injection tem-
perature override setpoint. If any of the above condi-
tions are not satisfied, then the oil flow analog out
-
put will be 4mA, which corresponds to 100 % valve
open.
Heat Pump:
• Enables the option for Heat Pump. The maintenance
Schedule for a Heat Pump Compressors is different &
hence the maintenance Chart is modified when the
Heat Pump option is selected
Discharge Pressure (Psig):
•
This setpoint defines a value for the Discharge
Pressure. This is typically used to determine the ser-
vice interval to Inspect a compressor’s Maintenance
Item in the Maintenance Chart Page of the
Maintenance Screen.
Differential Pressure (Psig):
•
This setpoint defines the value for the Differential
Pressure. This is typically used to determine the ser-
vice interval to Inspect a compressor’s Maintenance
Item in the Maintenance Chart Page of the
Maintenance Screen.
Daily Auto Backup Settings
The Vission 20/20 can backup the database every day
at a configured time. The following section defines the
time setpoints for database backup activity, see Figure
19-4.
Hour:
• Entry box to set the database backup hours. AM or
PM drop-down box will be available if the 12 hour for-
mat is selected.
Содержание Vilter Vission 20/20
Страница 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Страница 2: ......
Страница 4: ......
Страница 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Страница 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Страница 336: ......
Страница 337: ......