background image

QUICK START MANUAL

 

Easy Wall Controller (EWC) KBRCS01A 

 

Easy Wall Controller (EWC) provides: 

 

 

 

-

 

Room temperature measuring 

-

 

LOCAL / REMOTE control mode 

-

 

I, II, III, AUTO fan modes 

-

 

A/C system Switch ON/OFF 

-

 

Turning the dial for temperature variation 

 

 

 

 

Common features: 

-

 

Wall mounted Easy Wall Controller powered from Online Controller 

-

 

Modbus communication protocol  
(See Figure 3 – pin-out assignment) 

 

Mounting: 

-

 

wall mounting in dry internal environment 

-

 

approximately 1.5 m above the floor in a place with good air circulation 

-

 

do not mount where it can be affected by a draught, sunshine, heating devices or other factors 

 
Installation:  
 

This  device  may  be  installed  only  by  an  authorised  person  for  the  installation  and  service  of  Daikin  A/C  units.  Please 
follow the safety instructions in the A/C unit manual. 

 

1.

 

Turn  OFF  the  Online  Controller  -  unplug  Online 
Controller  system  cable  or  turn  the  A/C  isolator  OFF  
(NOT only ON/OFF button on A/C front panel). 

2.

 

Remove  EWC  front  panel  by  pressing  the  two  pawls 
on  bottom  or  top  side  (e.g.  by  screwdriver).  See 
Figure 2. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
3.

 

Mount back panel on the selected place on the wall. 

4.

 

Connect  Online  Controller  and  EWC  via  the  cable. 
Look at Figure 3 for pin-out assignment. 

5.

 

Then  turn ON  the Online  Controller  -  connect Online 
Controller system cable or turn the A/C isolator ON.   

 
6.

 

Set  the  communication  parameters  (Parity,  Address,  Communications  rate,  RS485  Line  Termination)  of  EWC  via 
configuration jumpers (Figures 4 and 5).  

Parity

 must be set to 

Even

.  

 
Procedure: 

a) Take out jumpers from JP1 to JP8 (LEDs are flickering irregularly under power supply) 
b) Place jumper on position JP1 (Even parity) 
c) Place jumper on position JP8 for confirm     
     Even parity (LEDs switch OFF) 

 

Address

 has to be set from 0 to 63. The weight of individual 

jumpers (IJ) for addressing and communication rate settings is 
listed on Figure 5. Procedure: 

a) Place jumper on the position JP4 for the address 8. 

 

Communication rate

 must be set to 

38400 bps

.  

Procedure: 

a) The jumper on position JP8 must be closed and 

jumper JP7 must be open – remove it. 
 

RS485 line Termination

. Procedure: 

a)  Keep  the  jumpers  J10  and  J11  unconnected  on  the  intermediate  station  or  connect  them  on  the  end 
station. See Figure 6. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
7.

 

Open  SETUP  menu  of  Online  Controller  (via 
web browser, for detailed instruction, please 
read  the  Quick  Start  manual  of  the  Online 
Controller).  At  Modbus  devices  setup  page 
(Figure  7)  choose  EWC35  from  Wall 
controller  selection  box  and  insert  Modbus 
address  8.  Confirm  your  selection  with  the 
Set button.  

Figure 1 

Figure 2 

Figure 4 

Figure 7 

Figure 5 

Figure 6 

Figure 3 

Отзывы: