[45]
Bus ctrl.
Controls output via bus. The state of the
output is set in
. If a bus timeout occurs,
the output state is retained.
[46]
Bus ctrl, 1 if
timeout
Controls output via bus. The state of the
output is set in
parameter 5-90 Digital & Relay
. If a bus timeout occurs, the
output state is set high (on).
[47]
Bus ctrl, 0 if
timeout
Controls output via bus. The state of the
output is set in
parameter 5-90 Digital & Relay
. If a bus timeout occurs, the
output state is set low (off).
[50]
On Reference
Active when a VLT® Advanced Cascade
Controller MCO 102 or VLT® Motion Control
MCO 305 is connected. The output is
controlled from option.
[51]
MCO controlled Active when a VLT® Advanced Cascade
Controller MCO 102 or VLT® Motion Control
MCO 305 is connected. The output is
controlled from option.
[54]
24V Encoder
Sim
Digital outputs 27 and 29 simulates an
single signal HTL encoder. Select source for
the signal generation in
NOTICE
[54] 24V Encoder Sim must be selected
in both
and
parameter 5-31 Terminal 29 Digital
Output
. This option is only available
for software version 48.XX.
[55]
Pulse output
[58]
Actual Position
[59]
Actual Position
4-20mA
[60]
Comparator 0
See
parameter group 13-1* Comparators
. If
comparator 0 is evaluated as true, the
output goes high. Otherwise, it is low.
[61]
Comparator 1
See
parameter group 13-1* Comparators
. If
Comparator 1 is evaluated as true, the
output goes high. Otherwise, it is low.
[62]
Comparator 2
See
parameter group 13-1* Comparators
. If
comparator 2 is evaluated as true, the
output goes high. Otherwise, it is low.
[63]
Comparator 3
See
parameter group 13-1* Comparators
. If
comparator 3 is evaluated as true, the
output goes high. Otherwise, it is low.
[64]
Comparator 4
See
parameter group 13-1* Comparators
. If
comparator 4 is evaluated as true, the
output goes high. Otherwise, it is low.
[65]
Comparator 5
See
parameter group 13-1* Comparators
. If
comparator 5 is evaluated as true, the
output goes high. Otherwise, it is low.
[70]
Logic rule 0
See
parameter group 13-4* Logic Rules
. If
logic rule 0 is evaluated as true, the output
goes high. Otherwise, it is low.
[71]
Logic rule 1
See
parameter group 13-4* Logic Rules
. If
logic rule 1 is evaluated as true, the output
goes high. Otherwise, it is low.
[72]
Logic rule 2
See
parameter group 13-4* Logic Rules
. If
logic rule 2 is evaluated as true, the output
goes high. Otherwise, it is low.
[73]
Logic rule 3
See
parameter group 13-4* Logic Rules
. If
logic rule 3 is evaluated as true, the output
goes high. Otherwise, it is low.
[74]
Logic rule 4
See
parameter group 13-4* Logic Rules
. If
logic rule 4 is evaluated as true, the output
goes high. Otherwise, it is low.
[75]
Logic rule 5
See
parameter group 13-4* Logic Rules
. If
logic rule 5 is evaluated as true, the output
goes high. Otherwise, it is low.
[80]
SL digital
output A
See parameter 13-52 SL Controller Action.
The output goes high whenever the smart
logic action
[38] Set dig
. out. A
high
is
executed. The output goes low whenever
the smart logic action
[32] Set dig. out
. A low
is executed.
[81]
SL digital
output B
See
parameter 13-52 SL Controller Action
. The
input goes high whenever the smart logic
action
[39] Set dig . out. B high
is executed.
The input goes low whenever the smart
logic action
[33] Set dig. out. B low
is
executed.
[82]
SL digital
output C
See
parameter 13-52 SL Controller Action
. The
input goes high whenever the smart logic
action
[40] Set dig. out. C high
is executed.
The input goes low whenever the smart
logic action
[34] Set dig. out. C low
is
executed.
[83]
SL digital
output D
See
parameter 13-52 SL Controller Action
. The
input goes high whenever the smart logic
action
[41] Set dig. out. D high
is executed.
The input goes low whenever the smart
logic action
[35] Set dig. out. D low
is
executed.
[84]
SL digital
output E
See
parameter 13-52 SL Controller Action
. The
input goes high whenever the smart logic
action
[42] Set dig. out. E high
is executed.
The input goes low whenever the smart
logic action
[36] Set dig. out. E low
is
executed.
[85]
SL digital
output F
See
parameter 13-52 SL Controller Action
. The
input goes high whenever the smart logic
action
[43] Set dig. out. F high
is executed.
The input goes low whenever the smart
logic action
[37] Set dig. out. F low
is
executed.
[90]
kWh counter
pulse
Sends a pulse (200 ms pulse width) to
output terminal whenever kWh counter
changes (
).
Parameter Descriptions
VLT
®
AutomationDrive FC 301/302
118
Danfoss A/S © 10/2018 All rights reserved.
MG33MP02