2.1.5 Parameter Set-up
The frequency converter can be used for practically all
assignments and offers 2 programming mode options:
•
Main menu mode.
•
Quick menu mode.
Main menu provides access to all parameters. Quick menu
takes the user through a few parameters, making it
possible to start operating the frequency converter.
Change a parameter in either main menu mode or quick
menu mode.
2.1.6 Quick Menu Key Functions
Press [Quick Menu] to enter a list of different areas
contained in the
Quick Menu
.
Select
Q1 My Personal Menu
to show the selected personal
parameters. These parameters are selected in
parameter 0-25 My Personal Menu
. Up to 50 different
parameters can be added in this menu.
130BC916.10
Q1 My Personal Menu
Q2 Quick Setup
Q4 Smart Setup
Q5 Changes Made
0RPM 0.00A 1(1)
Quick Menus
Illustration 2.13 Quick Menus
Select
Q2 Quick Setup
to go through a selection of
parameters to get the motor running almost optimally. The
default settings for the other parameters consider the
required control functions and the configuration of signal
inputs/outputs (control terminals).
The parameter selection is effected with the navigation
keys. The parameters in
are accessible.
Parameter
Setting
Parameter 0-01 Language
Parameter 1-20 Motor Power [kW]
[kW]
Parameter 1-22 Motor Voltage
[V]
Parameter 1-23 Motor Frequency
[Hz]
Parameter 1-24 Motor Current
[A]
Parameter 1-25 Motor Nominal Speed
[RPM]
Parameter 5-12 Terminal 27 Digital Input
[0] No function
1)
Parameter 1-29 Automatic Motor
Adaptation (AMA)
[1] Enable complete
AMA
Parameter 3-02 Minimum Reference
[RPM]
Parameter 3-03 Maximum Reference
[RPM]
Parameter 3-41 Ramp 1 Ramp Up Time
[s]
Parameter 3-42 Ramp 1 Ramp Down Time
[s]
Parameter 3-13 Reference Site
Table 2.2 Selection of Parameter
1) If terminal 27 is set to [0] No operation, no connection to +24 V
on terminal 27 is necessary.
Select
Changes made
to get information about:
•
The last 10 changes. Use the [
▲
] [
▼
] navigation
keys to scroll between the last 10 changed
parameters.
•
The changes made since default setting.
Select
Loggings
to get information about the show line
readouts. The information is shown as graphs.
Only parameters selected in
parameter 0-20 Display Line 1.1
Small
and
parameter 0-24 Display Line 3 Large
can be
viewed. It is possible to store up to 120 samples in the
memory for later reference.
How to Program
Programming Guide
MG33MP02
Danfoss A/S © 10/2018 All rights reserved.
17