5-40 Function Relay
Option:
Function:
[224] Position Limit
NOTICE
This option is available only with
software version 48.XX.
The position error exceeds the value in
parameter 4-71 Maximum Position Error
for the time set in
parameter 4-72 Position Error Timeout
[225] Position Error
NOTICE
This option is available only with
software version 48.XX.
The position is outside the limits set in
parameter 3-06 Minimum Position
and
parameter 3-07 Maximum Position
.
[226] Touch on Target
NOTICE
This option is available only with
software version 48.XX.
Target position is reached in touch
probe position mode.
[227] Touch Activated
NOTICE
This option is available only with
software version 48.XX.
Touch probe positioning active. The
frequency converter monitors the
touch probe sensor input.
[231] In Power Lim.
Mot.
[232] In Power Lim.
Gen.
[233] In Power Limit
5-41 On Delay, Relay
Array [20]
Range:
Function:
0.01 s
*
[0.01 -
600 s]
Enter the delay of the relay cut-in time.
Select 1 of 2 internal mechanical relays in
an array function. See
for details.
Selected
Event
Relay
output
Selected
Event
Relay
output
On Delay
P 5-41
On Delay
P 5-41
Off Delay
P 5-42
130BA171.10
Illustration 3.37 On Delay, Relay
5-42 Off Delay, Relay
Array[20]
Range:
Function:
0.01 s
*
[0.01 -
600 s]
Enter the delay of the relay cutout time. Select
1 of 2 internal mechanical relays in an array
function. See
for
details. If the selected event condition changes
before a delay timer expires, the relay output
is unaffected.
Selected
Event
Relay
output
On Delay
P 5-41
Off Delay
P 5-42
130BA172.10
Illustration 3.38 Off Delay, Relay
If the selected event condition changes before the on
delay or off delay timer expires, the relay output is
unaffected.
3.6.5 5-5* Pulse Input
The pulse input parameters are used to define an
appropriate window for the impulse reference area by
configuring the scaling and filter settings for the pulse
inputs. Input terminals 29 or 33 act as frequency reference
inputs. Set terminal 29 (
parameter 5-13 Terminal 29 Digital
Input
) or terminal 33 (
parameter 5-15 Terminal 33 Digital
Input
) to
[32] Pulse input
. If terminal 29 is used as an input,
set
parameter 5-01 Terminal 27 Mode
to
[0] Input
.
Parameter Descriptions
VLT
®
AutomationDrive FC 301/302
128
Danfoss A/S © 10/2018 All rights reserved.
MG33MP02
3
3