6-71 Terminal X45/1 Min. Scale
Range:
Function:
Hz) is required at 25% of the maximum output
value, then program 25%. Scaling values up to
100% can never exceed the corresponding setting
in
parameter 6-72 Terminal X45/1 Max. Scale
6-72 Terminal X45/1 Max. Scale
Range:
Function:
100
%
*
[0 -
200 %
]
Scale the maximum output of the selected analog
signal at terminal X45/1. Set the value to the
maximum value of the current signal output.
Scale the output to give a current lower than 20
mA at full scale, or 20 mA at an output below
100% of the maximum signal value. If 20 mA is
the required output current at a value between 0–
100% of the full-scale output, program the
percentage value in the parameter, for example
50% = 20 mA. If a current 4–20 mA is required at
maximum output (100%), calculate the percentage
value as follows (example where required
maximum output is 10 mA):
I
RANGE
mA
I
DESIRED MAX
mA x 100 %
= 20 − 4 mA
10 mA x 100 % = 160 %
130BA877.10
[mA]
0%
20
0/4
100%
Current
Analogue
output Min
Scale
par. 6-71
Variable for
output
example:Speed
[RPM]
Analogue
Output Max
Scale
par. 6-72
Illustration 3.46 Output Maximum Scale
6-73 Terminal X45/1 Bus Control
Range:
Function:
0 %
*
[0 - 100 %] Holds the level of analog output 3 (terminal
X45/1) if controlled by bus.
6-74 Terminal X45/1 Output Timeout Preset
Range:
Function:
0 %
*
[0 -
100 %]
Holds the preset level of analog output 3
(terminal X45/1).
If there is a fieldbus timeout and a timeout
function is selected in
, the output is preset to this level.
3.7.9 6-8* Analog Output 4 MCB 113
Parameters for configuring the scaling and limits for analog
output 4, terminals X45/3 and X45/4. Analog outputs are
current outputs: 0/4 to 20 mA. Resolution on analog
output is 11 bit.
6-80 Terminal X45/3 Output
Option:
Function:
Select the function of terminal
X45/3 as an analog current output.
[0]
No operation
Same selections available as for
parameter 6-70 Terminal X45/1
Output
[52]
MCO 0-20mA/0-10V
[100] Output frequency
[101] Reference
[102] Feedback
[103] Motor Current
[104] Torque rel to limit
[105] Torq relate to rated
[106] Power
[107] Speed
[108] Torque
[109] Max Out Freq
[113] PID Clamped Output
[119] Torque % lim
[130] Output freq. 4-20mA
[131] Reference 4-20mA
[132] Feedback 4-20mA
[133] Motor cur. 4-20mA
[134] Torq.% lim 4-20 mA
[135] Torq.% nom 4-20mA
[136] Power 4-20mA
[137] Speed 4-20mA
[138] Torque 4-20mA
[139] Bus ctrl. 0-20 mA
[140] Bus ctrl. 4-20 mA
[141] Bus ctrl 0-20mA t.o.
[142] Bus ctrl 4-20mA t.o.
[149] Torque % lim 4-20mA
[150] Max Out Fr 4-20mA
Parameter Descriptions
VLT
®
AutomationDrive FC 301/302
142