Number Description
Warning
Alarm/
trip
Alarm/
trip lock
Parameter
reference
1
10 volts low
X
–
–
–
2
Live zero error
(X)
(X)
–
Parameter 6-01 Live Zero Timeout Function
3
No motor
(X)
–
–
Parameter 1-80 Function at Stop
4
Mains phase loss
(X)
(X)
(X)
Parameter 14-12 Response to Mains
Imbalance
5
DC-link voltage high
X
–
–
–
6
DC-link voltage low
X
–
–
–
7
DC overvoltage
X
X
–
–
8
DC undervoltage
X
X
–
–
9
Inverter overloaded
X
X
–
–
10
Motor ETR overtemperature
(X)
(X)
–
Parameter 1-90 Motor Thermal Protection
11
Motor thermistor overtemperature
(X)
(X)
–
Parameter 1-90 Motor Thermal Protection
12
Torque limit
X
X
–
–
13
Overcurrent
X
X
X
–
14
Ground fault
X
X
–
–
15
Hardware mismatch
–
X
X
–
16
Short circuit
–
X
X
–
17
Control word timeout
(X)
(X)
–
Parameter 8-04 Control Word Timeout
Function
20
Temp. input error
–
X
–
–
21
Param error
–
X
–
22
Hoist mech. brake
(X)
(X)
–
Parameter group 2-2* Mechanical Brake
23
Internal fans
X
–
–
–
24
External fans
X
–
–
–
25
Brake resistor short-circuited
X
–
–
–
26
Brake resistor power limit
(X)
(X)
–
Parameter 2-13 Brake Power Monitoring
27
Brake chopper short-circuited
X
X
–
–
28
Brake check
(X)
(X)
–
Parameter 2-15 Brake Check
29
Heat sink temp
X
X
X
–
30
Motor phase U missing
(X)
(X)
(X)
Parameter 4-58 Missing Motor Phase Function
31
Motor phase V missing
(X)
(X)
(X)
Parameter 4-58 Missing Motor Phase Function
32
Motor phase W missing
(X)
(X)
(X)
Parameter 4-58 Missing Motor Phase Function
33
Inrush fault
X
X
–
34
Fieldbus communication fault
X
X
–
–
35
Option fault
–
–
X
–
36
Mains failure
X
X
–
–
37
Imbalance of supply voltage
X
–
–
38
Internal fault
X
X
–
39
Heat sink sensor
X
X
–
40
Overload of digital output terminal 27
(X)
–
–
Parameter 5-00 Digital I/O Mode
,
parameter 5-01 Terminal 27 Mode
41
Overload of digital output terminal 29
(X)
–
–
Parameter 5-00 Digital I/O Mode
,
parameter 5-02 Terminal 29 Mode
42
Ovrld X30/6-7
(X)
–
–
–
43
Ext. supply (option)
X
–
–
–
45
Ground fault 2
X
X
–
–
46
Pwr. card supply
–
X
X
–
47
24 V supply low
X
X
X
–
48
1.8 V supply low
–
X
X
–
50
AMA calibration failed
–
X
–
–
51
AMA check U
nom
and I
nom
–
X
–
–
52
AMA low I
nom
–
X
–
–
Troubleshooting
VLT
®
AutomationDrive FC 301/302
326
Danfoss A/S © 10/2018 All rights reserved.
MG33MP02