5-40 Function Relay
Option:
Function:
[29]
Brake ready, no
fault
Brake is ready for operation and there
are no faults.
[30]
Brake fault (IGBT)
Output is logic 1 when the brake IGBT
is short-circuited. Use this function to
protect the frequency converter if
there is a fault on the brake module.
Use the digital output/relay to cut out
the main voltage from the frequency
converter.
[31]
Relay 123
Digital output/relay is activated when
[0] Control Word
is selected in
parameter group 8-** Comm. and
Options
.
[32]
Mech brake ctrl
Selection of mechanical brake control.
When selected parameters in
parameter group 2-2* Mechanical Brake
are active. The output must be
reinforced to carry the current for the
coil in the brake. Usually solved by
connecting an external relay to the
selected digital output.
[33]
Safe stop active
NOTICE
This option is applicable for FC
302 only.
Indicates that the Safe Torque Off on
terminal 37 has been activated.
[35]
External Interlock
[36]
Control word bit
11
Activate relay 1 by control word from
fieldbus. No other functional impact in
the frequency converter. Typical
application: Controlling auxiliary device
from fieldbus. The function is valid
when
[0] FC profile
in
parameter 8-10 Control Word Profile
is
selected.
[37]
Control word bit
12
Activate relay 2 (FC 302 only) by
control word from fieldbus. No other
functional impact in the frequency
converter. Typical application:
Controlling auxiliary device from
fieldbus. The function is valid when
[0]
FC profile
in
parameter 8-10 Control
Word Profile
is selected.
[38]
Motor feedback
error
Failure in the speed feedback loop
from motor running in closed loop.
The output can eventually be used to
prepare switching the frequency
converter in open loop in an
emergency case.
5-40 Function Relay
Option:
Function:
[39]
Tracking error
When the difference between
calculated speed and actual speed in
parameter 4-35 Tracking Error
is larger
than selected, the digital output/relay
is active.
[40]
Out of ref range
Active when the actual speed is
outside settings in
parameter 4-52 Warning Speed Low
to
parameter 4-55 Warning Reference High
.
[41]
Below reference,
low
Active when actual speed is below
speed reference setting.
[42]
Above ref, high
Active when actual speed is above
speed reference setting.
[43]
Extended PID
Limit
[45]
Bus ctrl.
Controls digital output/relay via bus.
The state of the output is set in
parameter 5-90 Digital & Relay Bus
Control
. The output state is retained in
the event of bus timeout.
[46]
Bus ctrl, 1 if
timeout
Controls output via bus. The state of
the output is set in
parameter 5-90 Digital & Relay Bus
Control
. If a bus timeout occurs, the
output state is set high (on).
[47]
Bus ctrl, 0 if
timeout
Controls output via bus. The state of
the output is set in
parameter 5-90 Digital & Relay Bus
Control
. If a bus timeout occurs, the
output state is set low (Off).
[50]
On Reference
[51]
MCO controlled
Active when a VLT
®
Advanced Cascade
Controller MCO 102 or VLT
®
Motion
Control MCO 305 is connected. The
output is controlled from option.
[60]
Comparator 0
See
parameter group 13-1*
Comparators
. If comparator 0 in SLC is
true, the output goes high. Otherwise,
it is low.
[61]
Comparator 1
See
parameter group 13-1*
Comparators
. If comparator 1 in SLC is
true, the output goes high. Otherwise,
it is low.
[62]
Comparator 2
See
parameter group 13-1*
Comparators
. If comparator 2 in SLC is
true, the output goes high. Otherwise,
it is low.
[63]
Comparator 3
See
parameter group 13-1*
Comparators
. If comparator 3 in SLC is
Parameter Descriptions
Programming Guide
MG33MP02
Danfoss A/S © 10/2018 All rights reserved.