3-27 Virtual Master Max Ref
Range:
Function:
or fieldbus. Use
parameter group 3-6* Ramp 3
to
configure acceleration and deceleration.
3-28 Master Offset Speed Ref
Range:
Function:
1500
RPM
*
[0 -
65000
RPM]
NOTICE
This parameter is only available with
software version 48.XX.
Enter the speed reference for changing the
master offset in synchronization mode. To
ensure compatibility with software versions
48.01 and 48.10, this parameter is only
active when
is set to 0.
3.4.4 3-4* Ramp 1
For each of the 4 ramps (
parameter groups 3-4* Ramp 1
,
3-5* Ramp 2
,
3-6* Ramp 3
, and
3-7* Ramp 4
) configure the
ramp parameters:
•
Ramp type,
•
Ramping times (duration of acceleration and
deceleration), and
•
Level of jerk compensation for S-ramps.
Start by setting the linear ramping times corresponding to
and
P 3-*2
R amp ( X) D o wn
T ime (D ec)
P 4-13
H igh-limit
R PM
R ef er enc e
n
s
P 4-11
L o w limit
t
dec
T ime
P 3-*1
R amp ( X) Up
T ime ( A c c)
t
a cc
130BA872.11
Illustration 3.25 Linear Ramping Times
If S-ramps are selected, set the level of non-linear jerk
compensation required. Set jerk compensation by defining
the proportion of ramp-up and ramp-down times where
acceleration and deceleration are variable (that is,
increasing or decreasing). The S-ramp acceleration and
deceleration settings are defined as a percentage of the
actual ramp time.
130BA168.10
Ramp (X) S-Ramp
Ratio at Accel.End
Jerk compensated
Ramp (X)
Up Time
Ramp (X)
S-Ramp
Ratio at
Accel.End
Linear
Speed
Ramp (X)
Down Time
Ramp (X)
S-Ramp
Ratio at
Dec.End
Ramp (X) S-Ramp
Ratio at Dec.End
Illustration 3.26 Linear Ramping Times
3-40 Ramp 1 Type
Option:
Function:
NOTICE
If
[1] S-ramp Const Jerk
is selected and
the reference during ramping is changed,
the ramp time may be prolonged to
realize a jerk-free movement, which may
result in a longer start or stop time.
Extra adjustment of the S-ramp ratios or
switching initiators may be necessary.
Select the ramp type, depending on
requirements for acceleration/deceleration.
A linear ramp gives constant acceleration during
ramping. An S-ramp gives non-linear
acceleration, compensating for jerk in the
application.
[0]
*
Linear
[1]
S-ramp
Const
Jerk
Acceleration with lowest possible jerk.
[2]
S-ramp
Const
Time
S-ramp based on the values set in
parameter 3-41 Ramp 1 Ramp Up Time
and
parameter 3-42 Ramp 1 Ramp Down Time
.
3-41 Ramp 1 Ramp Up Time
Range:
Function:
Size
related
*
[ 0.01 -
3600 s]
Enter the ramp-up time, that is the
acceleration time from 0 RPM to the
synchronous motor speed n
S
. Select a ramp-
up time which prevents the output current
from exceeding the current limit in
during ramping.
The value 0.00 corresponds to 0.01 s in
speed mode. See ramp-down time in
parameter 3-42 Ramp 1 Ramp Down Time
.
Par . 3 − 41 =
t
acc
s x n
s
RPM
ref RPM
Parameter Descriptions
VLT
®
AutomationDrive FC 301/302
82
Danfoss A/S © 10/2018 All rights reserved.
MG33MP02
3
3