NOTICE
A change in mode via the digital inputs can only take
place if
parameter 23-08 Timed Actions Mode
is set for
[0]
Times Actions Auto
.
If commands are applied simultaneously to the digital
inputs for constant OFF and constant ON, the timed
actions mode changes to timed actions auto and the 2
commands are disregarded.
If
parameter 0-70 Date and Time
is not set or the
frequency converter is set to hand-on mode or OFF
mode (for example via the LCP), the timed actions mode
is changed to
[0] Disabled
.
The timed actions have a higher priority than the same
actions/commands activated by the digital inputs or the
smart logic controller.
The actions programmed in timed actions are merged with
corresponding actions from digital inputs, control word via
bus, and smart logic controller, according to merge rules
set up in
parameter group 8-5* Digital/Bus
.
NOTICE
Program the clock (
parameter group 0-7* Clock Settings
)
correctly for timed actions to function.
NOTICE
When mounting VLT
®
Analog I/O Option MCB 109, a
battery back-up of the date and time is included.
NOTICE
The PC-based configuration tool MCT 10 Set-up Software
comprises a special guide for easy programming of
timed actions.
23-00 ON Time
Array [10]
Range:
Function:
Size
related
*
[ 0 - 0 ] Sets the ON time for the timed action.
NOTICE
The frequency converter has no
back-up of the clock function. The
set date/time resets to default
(2000-01-01 00:00) after a power-
down unless a real-time clock-
module with back-up is installed. In
, it is
possible to program a warning if
the clock has not been set properly,
for example after a power-down.
23-01 ON Action
Array [10]
Option:
Function:
NOTICE
For options
[32] Set digital out
A low
–
[43] Set digital out F high
,
see also
parameter group 5-3*
Digital Outputs and parameter
group 5-4* Relays
.
Select the action during ON time.
See
for descriptions of the
options.
[0]
*
DISABLED
[1]
No action
[2]
Select set-up 1
[3]
Select set-up 2
[4]
Select set-up 3
[5]
Select set-up 4
[10] Select preset ref 0
[11] Select preset ref 1
[12] Select preset ref 2
[13] Select preset ref 3
[14] Select preset ref 4
[15] Select preset ref 5
[16] Select preset ref 6
[17] Select preset ref 7
[18] Select ramp 1
[19] Select ramp 2
[20] Select ramp 3
[21] Select ramp 4
[22] Run
[23] Run reverse
[24] Stop
[25] Qstop
[26] Dcstop
[27] Coast
[32] Set digital out A low
[33] Set digital out B low
[34] Set digital out C low
[35] Set digital out D low
[36] Set digital out E low
[37] Set digital out F low
[38] Set digital out A high
[39] Set digital out B high
[40] Set digital out C high
[41] Set digital out D high
[42] Set digital out E high
[43] Set digital out F high
[60] Reset Counter A
[61] Reset Counter B
Parameter Descriptions
Programming Guide
MG33MP02
Danfoss A/S © 10/2018 All rights reserved.