[96]
Reverse After
Ramp
NOTICE
This option is available only with
software version 48.XX.
Indicates if the direction of rotation should
be reversed. Depends on whether the speed
reference is positive or negative after the
ramp specified in
[98]
Virtual Master
Dir.
NOTICE
This option is available only with
software version 48.XX.
A virtual master signal that controls the
rotation direction of followers.
[120] Local ref active
Output is high when parameter 3-13
Reference Site = [2] Local.
Reference site set
in parameter 3-13
Reference Site
Local
reference
active
[120]
Remote
reference
active
[121]
Reference site:
Local parameter
3-13 Reference Site
[2] Local
1
0
Reference site:
Remote parameter
3-13 Reference Site
[1] Remote
0
1
Reference site:
Linked to Hand/
Auto
Hand
1
0
Hand
⇒
off
1
0
Auto
⇒
off
0
0
Auto
0
1
Table 3.20 Local Reference Active
[121] Remote ref
active
Output is high when
=
[1] Remote
or
[0] Linked to hand/auto
while the LCP is in
auto-on mode. See
[122] No alarm
Output is high when no alarm is present.
[123] Start command
activ
Output is high when there is an active start
command (that is via digital input bus
connection, hand-on, or auto-on), and no
stop or start command is active.
[124] Running reverse Output is high when the frequency
converter runs counterclockwise (the logical
product of the status bits running AND
reverse).
[125] Drive in hand
mode
Output is high when the frequency
converter is in
hand-on
mode (as indicated
by the LED light above [Hand On]).
[126] Drive in auto
mode
Output is high when the frequency
converter is in
auto-on
mode (as indicated
by the LED light above [Auto On]).
[151] ATEX ETR cur.
alarm
Selectable if
is set to
[20] ATEX ETR
or
[21]
Advanced ETR
. If
Alarm 164 ATEX ETR
cur.lim.alarm
is active, the output is 1.
[152] ATEX ETR freq.
alarm
Selectable if
is set to
[20] ATEX ETR
or
[21]
Advanced ETR
. If
Alarm 166 ATEX ETR
freq.lim.alarm
is active, the output is 1.
[153] ATEX ETR cur.
warning
[154] ATEX ETR freq.
warning
Selectable if
is set to
[20] ATEX ETR
or
[21]
Advanced ETR
. If
Warning 165, ATEX ETR
freq.lim.warning
is active, the output is 1.
[180] Clock Fault
[181] Prev.
Maintenance
[188] AHF Capacitor
Connect
The capacitors are turned on at 20%
(hysteresis of 50% gives an interval of 10–
30%). The capacitors are disconnected below
10%. The off delay is 10 s and restarts if the
nominal power goes above 10% during the
delay.
parameter 5-80 AHF Cap Reconnect
is used to guarantee a minimum off-
time for the capacitors.
[189] External Fan
Control
The internal logics for the internal fan
control is transferred to this output to make
it possible to control an external fan
(relevant for hp duct cooling).
[190] Safe Function
active
[191] Safe Opt. Reset
req.
[192] RS Flipflop 0
See
parameter group 13-1* Comparators
.
[193] RS Flipflop 1
See
parameter group 13-1* Comparators
.
[194] RS Flipflop 2
See
parameter group 13-1* Comparators
.
[195] RS Flipflop 3
See
parameter group 13-1* Comparators
.
[196] RS Flipflop 4
See
parameter group 13-1* Comparators
.
[197] RS Flipflop 5
See
parameter group 13-1* Comparators
.
[198] RS Flipflop 6
See
parameter group 13-1* Comparators
.
[199] RS Flipflop 7
See
parameter group 13-1* Comparators
.
[221] IGBT-cooling
Use this option for handling the overcurrent
trips. When the frequency converter detects
an overcurrent condition, it shows
alarm 13,
Overcurrent
and triggers a reset. If the
overcurrent condition occurs the third time
in a row, the frequency converter shows
alarm 13, Overcurrent
and initiates a 3-
minute delay before the next reset.
Parameter Descriptions
Programming Guide
MG33MP02
Danfoss A/S © 10/2018 All rights reserved.
119
3
3