3.13.11 13-9* User-defined Alerts and
Readouts
Parameters in this group allow the configuration of
application-specific messages, warnings, and alarms.
Use the following parameters to configure the frequency
converter to show a message and perform an action when
a specific event occurs:
•
Parameter 13-90 Alert Trigger
– the event that
triggers the user-defined action and message.
•
Parameter 13-91 Alert Action
– the action that the
frequency converter performs when the event
defined in
parameter 13-90 Alert Trigger
occurs.
•
Parameter 13-92 Alert Text
– the text that the
frequency converter shows in the display when
the event defined in
parameter 13-90 Alert Trigger
occurs.
For example, consider the following use case:
If there is an active signal on digital input 32, the
frequency converter shows the message
Valve 5 open
and
ramps down to a stop.
To achieve this configuration, make the following settings:
•
Parameter 13-90 Alert Trigger
=
[37] Digital input
DI32
.
•
Parameter 13-91 Alert Action
=
[5] Stop & warning
.
•
Parameter 13-92 Alert Text
= Valve 5 open.
3.13.12 13-90 Alert Trigger
13-90 Alert Trigger
Array [10]
Select the event that triggers the user-defined action and
message.
Option:
Function:
[0]
*
False
[1]
True
[18]
Reversing
[22]
Comparator 0
[23]
Comparator 1
[24]
Comparator 2
[25]
Comparator 3
[26]
Logic rule 0
[27]
Logic rule 1
[28]
Logic rule 2
[29]
Logic rule 3
[30]
SL Time-out 0
[31]
SL Time-out 1
[32]
SL Time-out 2
[33]
Digital input DI18
[34]
Digital input DI19
[35]
Digital input DI27
[36]
Digital input DI29
[37]
Digital input DI32
13-90 Alert Trigger
Array [10]
Select the event that triggers the user-defined action and
message.
Option:
Function:
[38]
Digital input DI33
[50]
Comparator 4
[51]
Comparator 5
[60]
Logic rule 4
[61]
Logic rule 5
[70]
SL Time-out 3
[71]
SL Time-out 4
[72]
SL Time-out 5
[73]
SL Time-out 6
[74]
SL Time-out 7
13-91 Alert Action
Array [10]
Select the action that the frequency converter performs when
the event defined in
occurs.
Option:
Function:
[0]
*
Info
[1]
Warning
[2]
Freeze output
[3]
Freeze output & warn
[4]
Stop
[5]
Stop & warning
[6]
Jogging
[7]
Jogging & warning
[8]
Max speed
[9]
Max speed & warn
[10]
Stop and trip
[11]
Stop and trip w manual
reset
[12]
Trip
[13]
Trip w manual reset
[14]
Trip Lock
13-92 Alert Text
Range:
Function:
Size
related
*
[0 -
20 ]
Array [10]
Enter the text that the frequency
converter shows in the display when the
event defined in
occurs.
13-97 Alert Alarm Word
Range:
Function:
0
*
[0 - 4294967295 ] Shows the alarm word of a user-defined
alarm in hex code.
Parameter Descriptions
Programming Guide
MG33MP02
Danfoss A/S © 10/2018 All rights reserved.
189