13-16 RS-FF Operand R
Option:
Function:
[223] On Target
NOTICE
This option is available only
with software version 48.20
and newer.
Positioning is completed and the
on-target signal is sent when the
actual position is within
parameter 3-05 On Reference
Window
for the duration of
and
the actual speed does not exceed
parameter 3-05 On Reference
Window
[224] Position Error
NOTICE
This option is available only
with software version 48.20
and newer.
The position error exceeds the
value in
for the time set in
parameter 4-72 Position Error
Timeout
[225] Position Limit
NOTICE
This option is available only
with software version 48.20
and newer.
The position is outside the limits
set in
and
parameter 3-07 Maximum Position
[226] Touch on Target
NOTICE
This option is available only
with software version 48.20
and newer.
Target position is reached in touch
probe position mode.
[227] Touch Activated
NOTICE
This option is available only
with software version 48.20
and newer.
Touch probe positioning active. The
frequency converter monitors the
touch probe sensor input.
3.13.5 13-2* Timers
Use the result (true or false) from timers directly to define
an event (see
parameter 13-51 SL Controller Event
), or as
boolean input in a logic rule (see
parameter 13-40 Logic
Rule Boolean 1
,
parameter 13-42 Logic Rule Boolean 2
, or
parameter 13-44 Logic Rule Boolean 3
). A timer is only false
when started by an action (for example
[29] Start timer 1
)
until the timer value entered in this parameter has elapsed.
Then it becomes true again.
All parameters in this parameter group are array
parameters with index 0–2. Select index 0 to program
timer 0, select index 1 to program timer 1, and so on.
13-20 SL Controller Timer
Range:
Function:
Size
related
*
[ 0 -
0 ]
Enter the value to define the duration of
the false output from the programmed
timer. A timer is only false if it is started by
an action (that is
[29] Start timer 1
) and
until the given timer value has elapsed.
3.13.6 13-4* Logic Rules
Combine up to 3 boolean inputs (true/false inputs) from
timers, comparators, digital inputs, status bits, and events
using the logical operators AND, OR, and NOT. Select
boolean inputs for the calculation in
parameter 13-40 Logic
Rule Boolean 1
,
parameter 13-42 Logic Rule Boolean 2
, and
parameter 13-44 Logic Rule Boolean 3
. Define the operators
used to logically combine the selected inputs in
parameter 13-41 Logic Rule Operator 1
and
parameter 13-43 Logic Rule Operator 2
.
. . .
. . .
. . .
. . .
Par. 13-43
Logic Rule Operator 2
Par. 13-41
Logic Rule Operator 1
Par. 13-40
Logic Rule Boolean 1
Par. 13-42
Logic Rule Boolean 2
Par. 13-44
Logic Rule Boolean 3
130BB673.10
Illustration 3.57 Logic Rules
Priority of calculation
The results of
parameter 13-40 Logic Rule Boolean 1
,
parameter 13-41 Logic Rule Operator 1
, and
parameter 13-42 Logic Rule Boolean 2
are calculated first.
The outcome (true/false) of this calculation is combined
with the settings of
parameter 13-43 Logic Rule Operator 2
and
parameter 13-44 Logic Rule Boolean 3
, yielding the final
result (true/false) of the logic rule.
Parameter Descriptions
Programming Guide
MG33MP02
Danfoss A/S © 10/2018 All rights reserved.
177