0-30 Unit for User-defined Readout
Option:
Function:
[171] lb/in²
[172] in WG
[173] ft WG
[176] kpsi
[177] MPa
[178] kBar
[180] HP
0-31 Min Value of User-defined Readout
Range:
Function:
0 CustomRea-
doutUnit
*
[ -999999.99 -
par. 0-32
CustomRea-
doutUnit]
This parameter sets the
minimum value of the custom-
defined readout (occurs at 0
speed). Only possible to set
different from 0 when selecting
a linear unit in
parameter 0-30 Unit for User-
defined Readout
. For quadratic
and cubic units, the minimum
value is 0.
0-32 Max Value of User-defined Readout
Range:
Function:
100 Custom-
ReadoutUnit
*
[ par. 0-31 -
999999.99
CustomRea-
doutUnit]
This parameter sets the
maximum value to be shown
when the speed of the motor
has reached the set value for
parameter 4-13 Motor Speed
High Limit [RPM]
or
parameter 4-14 Motor Speed
High Limit [Hz]
(depends on
setting in
parameter 0-02 Motor
Speed Unit
).
0-33 Source for User-defined Readout
Option:
Function:
Enter the source of the
user-defined readout.
[105]
Torq relate to rated
[143]
PID Clamped Output
4-20mA
[240]
*
Default Source
0-37 Display Text 1
Range:
Function:
0
*
[0 -
25 ]
Enter a text which can be viewed in the graphical
display by selecting
[37] Display Text 1
in
•
Parameter 0-20 Display Line 1.1 Small
,
•
Parameter 0-21 Display Line 1.2 Small
,
•
Parameter 0-22 Display Line 1.3 Small
,
•
Parameter 0-23 Display Line 2 Large
, or
•
Parameter 0-24 Display Line 3 Large
.
0-38 Display Text 2
Range:
Function:
0
*
[0 -
25 ]
Enter a text which can be viewed in the graphical
display by selecting
[38] Display Text 2
in
•
Parameter 0-20 Display Line 1.1 Small
,
•
Parameter 0-21 Display Line 1.2 Small
,
•
Parameter 0-22 Display Line 1.3 Small
,
•
Parameter 0-23 Display Line 2 Large
, or
•
Parameter 0-24 Display Line 3 Large
.
0-39 Display Text 3
Range:
Function:
0
*
[0 -
25 ]
Enter a text which can be viewed in the graphical
display by selecting
[39] Display Text 3
in
•
Parameter 0-20 Display Line 1.1 Small
,
•
Parameter 0-21 Display Line 1.2 Small
,
•
Parameter 0-22 Display Line 1.3 Small
,
•
Parameter 0-23 Display Line 2 Large
, or
•
Parameter 0-24 Display Line 3 Large
.
3.1.5 0-4* LCP Keypad
Enable, disable, and password protect individual keys on
the LCP.
0-40 [Hand on] Key on LCP
Option:
Function:
[0] Disabled
No effect when [Hand On] is pressed. Select
[0]
Disabled
to avoid accidental start of the
frequency converter in hand-on mode.
[1] Enabled
The LCP switches to hand-on mode directly
when [Hand On] is pressed.
[2] Password
After pressing [Hand On] a password is
required. If
parameter 0-40 [Hand on] Key on
LCP
is included in
My Personal Menu
, define the
password in
parameter 0-65 Personal Menu
Password
. Otherwise define the password in
parameter 0-60 Main Menu Password
.
[3] Hand Off/On When [Hand On] is pressed once, the LCP
switches to Off mode. When pressed again, the
LCP switches to hand-on mode.
[4] Hand Off/On
w. Passw.
Same as option
[3] Hand Off/On
but a
password is required (see option
[2] Password
).
[9] Enabled, ref
= 0
0-41 [Off] Key on LCP
Option:
Function:
[0] Disabled Avoids accidental stop of the frequency converter.
[1] Enabled
Parameter Descriptions
VLT
®
AutomationDrive FC 301/302
38
Danfoss A/S © 10/2018 All rights reserved.
MG33MP02
3
3
Содержание VLT AutomationDrive FC 302