Number Description
Warning
Alarm/
trip
Alarm/
trip lock
Parameter
reference
166
ATEX ETR freq.lim.alarm
–
X
–
–
210
Position tracking
X
X
–
Parameter 4-70 Position Error Function
parameter 4-71 Maximum Position Error
,
parameter 4-72 Position Error Timeout
211
Position limit
X
X
–
Parameter 3-06 Minimum Position
,
parameter 3-07 Maximum Position
parameter 4-73 Position Limit Function
212
Homing not done
–
X
–
Parameter 17-80 Homing Function
213
Homing timeout
–
X
–
214
No sensor input
–
X
–
–
215
Start fwd/rev
X
X
–
Parameter 4-74 Start Fwd/Rev Function
216
Touch timeout
–
X
–
220
Configuration File Version not supported
X
–
–
–
246
Pwr.card supply
–
–
X
–
250
New spare part
–
–
X
–
251
New type code
–
X
X
–
430
PWM Disabled
–
X
–
–
Table 6.1 Alarm/Warning Code List
(X) Dependent on parameter.
1) Cannot be auto reset via parameter 14-20 Reset Mode.
A trip is the action following an alarm. The trip coasts the motor and is reset by pressing [Reset] or by a digital input
(
parameter group 5-1* Digital Inputs
). The original event that caused an alarm cannot damage the frequency converter or
cause dangerous conditions. A trip lock is an action when an alarm occurs, which could damage the frequency converter or
connected parts. A trip lock situation can only be reset by cycling power.
Warning
Yellow
Alarm
Flashing red
Trip locked
Yellow and red
Table 6.2 Indicator Light
Bit Hex
Dec
Alarm word
Alarm word 2
Warning word
Warning
word 2
Extended
status word
Alarm Word Extended Status Word
0
00000001
1
Brake check (A28) Servicetrip, read/
write
Brake check (W28) Start delayed Ramping
1
00000002
2
Pwr.card temp
(A69)
Servicetrip,
(reserved)
Pwr.card temp
(A69)
Stop delayed AMA running
2
00000004
4
Earth fault (A14)
Servicetrip,
typecode/
sparepart
Earth fault (W14)
Reserved
Start CW/CCW
start_possible is active, when the DI
selections [12] OR [13] are active
and the requested direction
matches the reference sign
3
00000008
8
Ctrl.card temp
(A65)
Servicetrip,
(reserved)
Ctrl.card temp
(W65)
Reserved
Slow down
slow down command active, for
example via CTW bit 11 or DI
4
00000010
16
Ctrl. word TO
(A17)
Servicetrip,
(reserved)
Ctrl. word TO
(W17)
Catch up
catch up command active, for
example via CTW bit 12 or DI
5
00000020
32
Overcurrent (A13) Reserved
Overcurrent (W13) Reserved
Feedback high
feedback >
parameter 4-57 Warning
Feedback High
Troubleshooting
VLT
®
AutomationDrive FC 301/302
328