15-14 Samples Before Trigger
Range:
Function:
50
*
[0 - 100 ] Before a trigger event, enter the percentage of
all samples which should be retained in the log.
See also
and
15-15 Service Log Sampling
See Service log.
By enabling this parameter, a text message is displayed in the
drive when the service log runs full:
Clear logs, Service log full: 28
[M26]
. The message recommends to clear the log.
Option:
Function:
[0]
*
Disabled
[1]
Enabled
Enable message
3.15.3 Service Log
The service log functionality saves detailed log information
of a 5-second interval in cases when certain alarms occur.
Service technicians can analyze this information to
troubleshoot and optimize the frequency converter.
The frequency converter can save up to 24 service log
records in the flash memory.
Find the list of alarms that trigger a service log record in
chapter 3.15.6 Alarms that Trigger a Service Log Record
Application-dependent trips/alarms, for example, Safe
Torque Off, do not trigger a service log record.
Sampling rate
There are 2 periods with different sampling rates:
•
Slow samples: 20 samples at a rate of 250 ms
resulting in 5 s of history before the trip.
•
Fast samples: 50 samples at a rate of 5 ms
resulting in 250 ms of detailed history before the
trip.
NOTICE
To enable the real-time clock (RTC) stamp, use the real-
time clock module. If real-time clock is not available, the
operating time in
parameter 15-32 Fault Log: Time
is
recorded.
The service log contains the elements shown in
.
# Alarm log data
Parameter number
1 Time of trip (1 of the
values):
•
Priority real-time
clock (if available).
•
Priority operating
time (if RTC is not
available).
Parameter 0-89 Date and Time
Readout
or
parameter 15-32 Fault
Log: Time
2 Alarm code
Parameter 15-30 Fault Log: Error
Code
3 Frequency
Parameter 16-13 Frequency
4 Speed (RPM)
Parameter 16-17 Speed [RPM]
5 Reference (%)
Parameter 16-02 Reference %
7 DC-link voltage
Parameter 16-30 DC Link Voltage
9 Motor phase U current
Parameter 16-45 Motor Phase U
Current
10 Motor phase V current
Parameter 16-46 Motor Phase V
Current
11 Motor phase W current
Parameter 16-47 Motor Phase W
Current
12 Motor phase voltage
Parameter 16-12 Motor Voltage
15 Control word
Parameter 16-00 Control Word
16 Status word
Parameter 16-03 Status Word
Table 3.28 Service Log Data
3.15.4 Clearing the Service Log
The flash memory stores up to 24 records. To save more
logs, clear the service log memory.
To clear the service log:
1.
In
parameter 14-22 Operation Mode
, select option
[5] Clear Service Log
.
2.
Power cycle the frequency converter. Clearing the
service log extends the power-up time by approx-
imately 1 s.
Save the service log records using the MCT 10 Set-up
Software before clearing the service log.
Clear the service log after a commissioning to remove any
alarms that occurred during the testing.
Service log indication
Parameter 16-42 Service Log Counter
shows the number of
service logs stored in the memory.
The frequency converter indicates a full service log
memory in 1 of the following ways:
•
The LCP shows the message:
Clear logs Service log full: 28 [M26]
•
Bit 25 is set high in
parameter 16-96 Maintenance
Word
(0x2000000).
Parameter Descriptions
VLT
®
AutomationDrive FC 301/302
204
Danfoss A/S © 10/2018 All rights reserved.
MG33MP02
3
3