5-40 Function Relay
Option:
Function:
true, the output goes high. Otherwise,
it is low.
[64]
Comparator 4
See
parameter group 13-1*
Comparators
. If comparator 4 in SLC is
true, the output goes high. Otherwise,
it is low.
[65]
Comparator 5
See
parameter group 13-1* Smart Logic
Control
. If comparator 5 in SLC is true,
the output goes high. Otherwise, it is
low.
[70]
Logic rule 0
See
parameter group 13-4* Smart Logic
Control
. If logic rule 0 in SLC is true,
the output goes high. Otherwise, it is
low.
[71]
Logic rule 1
See
parameter group 13-4* Smart Logic
Control
. If logic rule 1 in SLC is true,
the output goes high. Otherwise, it is
low.
[72]
Logic rule 2
See
parameter group 13-4* Smart Logic
Control
. If logic rule 2 in SLC is true,
the output goes high. Otherwise, it is
low.
[73]
Logic rule 3
See
parameter group 13-4* Smart Logic
Control
. If logic rule 3 in SLC is true,
the output goes high. Otherwise, it is
low.
[74]
Logic rule 4
See
parameter group 13-4* Smart Logic
Control
. If logic rule 4 in SLC is true,
the output goes high. Otherwise, it is
low.
[75]
Logic rule 5
See
parameter group 13-4* Smart Logic
Control
. If logic rule 5 in SLC is true,
the output goes high. Otherwise, it is
low.
[80]
SL digital output
A
See
parameter 13-52 SL Controller
Action
. Output A is low on smart logic
action
[32]
. Output A is high on smart
logic action
[38]
.
[81]
SL digital output
B
See
parameter 13-52 SL Controller
Action
. Output B is low on smart logic
action
[33]
. Output B is high on smart
logic action
[39]
.
[82]
SL digital output
C
See
parameter 13-52 SL Controller
Action
. Output C is low on smart logic
action
[34]
. Output C is high on smart
logic action
[40]
.
[83]
SL digital output
D
See
parameter 13-52 SL Controller
Action
. Output D is low on smart logic
action
[35]
. Output D is high on smart
logic action
[41]
.
5-40 Function Relay
Option:
Function:
[84]
SL digital output
E
See
. Output E is low on smart logic
action
[36]
. Output E is high on smart
logic action
[42]
.
[85]
SL digital output
F
See
parameter 13-52 SL Controller
Action
. Output F is low on smart logic
action
[37]
. Output F is high on smart
logic action
[43]
.
[96]
Reverse After
Ramp
NOTICE
This option is available only with
software version 48.XX.
See the description in
chapter 3.6.3 5-3* Digital Outputs
.
[98]
Virtual Master Dir.
NOTICE
This option is available only with
software version 48.XX.
See the description in
chapter 3.6.3 5-3* Digital Outputs
.
[120] Local ref active
Output is high when
=
[2] Local
or when
parameter 3-13 Reference Site
=
[0] Linked to hand auto
at the same
time as the LCP is in
hand-on
mode.
Reference site
set in
parameter 3-13
Reference Site
Local
referenc
e
active
[120]
Remote
reference
active
[121]
Reference site:
Local
[2]
Local
1
0
Reference site:
Remote
[1]
Remote
0
1
Reference site:
Linked to Hand/
Auto
Hand
1
0
Hand
⇒
off
1
0
Auto
⇒
off
0
0
Auto
0
1
Table 3.21 Local Reference Active
Parameter Descriptions
VLT
®
AutomationDrive FC 301/302
126
Danfoss A/S © 10/2018 All rights reserved.
MG33MP02
3
3