3-15 Reference Resource 1
Option:
Function:
Select the speed reference source in
parameter 3-15
when
parameter 1-00 Configuration Mode
is set
to
[9]
in positioning mode.
NOTICE
The options 3, 4, 5, 6, 12, 13, 14 are
only available with software version
48.XX
[0]
No function
[1]
Analog Input 53
[2]
Analog Input 54
[3]
24V encoder
32/33
[4]
MCB 102
[5]
MCB 103
[6]
Virtual Master
[7]
Frequency input
29
[8]
Frequency input
33
[11] Local bus
reference
Reference from terminals 68 and 69.
[12] Preset Reference Select this option to set the speed
reference in
together with the preset target
in
to calculate
speed profile for positioning.
[13] 24V encoder
27/29
[14] MCB 102
Absolute
[20] Digital
pot.meter
[21] Analog input
X30/11
VLT
®
General Purpose I/O MCB 101
[22] Analog input
X30/12
VLT
®
General Purpose I/O MCB 101
[29] Analog Input
X48/2
3-16 Reference Resource 2
Option:
Function:
NOTICE
The options 3, 4, 5, 6, 12, 13, and 14
are only available for software version
48.XX.
Select the reference input to be used for the
2
nd
reference signal.
,
parameter 3-16 Reference Resource
, and
parameter 3-17 Reference Resource 3
3-16 Reference Resource 2
Option:
Function:
define up to 3 different reference signals.
The sum of these reference signals defines
the actual reference.
When
parameter 1-00 Configuration Mode
is
set to
[10]
for synchronizing mode, configure
parameter 3-16 to select the source for
master position.
When
parameter 1-00 Configuration Mode
is
set to
[9]
for positioning mode, configure
parameter 3-16 to select the source for
target position.
[0]
No function
[1]
Analog Input
53
[2]
Analog Input
54
[3]
24V encoder
32/33
Single signal generated from 24V High
Threshold Logic (HTL) encoder connected to
terminals 32 and 33. Configure the 24V
encoder interface in
Parameter group 5.7*
24V Encoder Option
.
Program terminals 32/33 to
[0] No operation
.
[4]
MCB 102
This is only available for VLT
®
Encoder
Option MCB 102. Configure the encoder
interface in
parameter groups 17-0*, 17-1*
and 17-2*
.
[5]
MCB 103
This is only available for VLT
®
Resolver
Option MCB 103. Configure the resolver
interface in
parameter groups 17-5*
.
[6]
Virtual Master Master signal for the drive which hosts the
virtual master without an external
connection.
[7]
Frequency
input 29
[8]
Frequency
input 33
[11] Local bus
reference
Reference from terminals 68 and 69.
[12] Preset
Reference
[13] 24V encoder
27/29
Single signal generated from 24V High
Threshold Logic (HTL) encoder connected to
terminals 27 and 29. Configure the 24V
encoder interface in
parameter group 5.7*
24V Encoder Input
.
Program terminals 27/29 to
[0] No operation
.
[14] MCB 102
Absolute
The option is only available for VLT
®
Encoder
Option MCB 102 with version 4.00 and
newer and when
is set to option
[1] Two Encoders
.
Parameter Descriptions
Programming Guide
MG33MP02
Danfoss A/S © 10/2018 All rights reserved.
79
3
3