1-34 Rotor Leakage Reactance (X2)
Range:
Function:
Size
related
*
[ 0.0400 -
400.0000
Ohm]
NOTICE
This parameter is only relevant for
asynchronous motors.
Set the rotor leakage reactance of the
motor using 1 of these methods:
•
Run an AMA on a cold motor.
The frequency converter
measures the value from the
motor.
•
Enter the X
2
value manually.
Obtain the value from the
motor supplier.
•
Use the X
2
default setting. The
frequency converter establishes
the setting based on the motor
nameplate data.
See
.
NOTICE
The parameter value is updated
after each torque calibration if
option
[3] 1st start with store
or
option
[4] Every start with store
is
selected in
.
1-35 Main Reactance (Xh)
Range:
Function:
Size
related
*
[ 1.0000 -
10000.0000
Ohm]
Set the main reactance of the motor
using 1 of these methods:
1.
Run an AMA on a cold motor.
The frequency converter
measures the value from the
motor.
2.
Enter the X
h
value manually.
Obtain the value from the
motor supplier.
3.
Use the X
h
default setting.
The frequency converter
establishes the setting based
on the motor nameplate data.
1-36 Iron Loss Resistance (Rfe)
Range:
Function:
Size
related
*
[ 0 -
10000.000
Ohm]
Enter the equivalent iron loss
resistance (R
Fe
) value to compensate
for iron loss in the motor.
The R
Fe
value cannot be found by
performing an AMA.
1-36 Iron Loss Resistance (Rfe)
Range:
Function:
The R
Fe
value is especially important in
torque control applications. If R
Fe
is
unknown, leave
on default setting.
1-37 d-axis Inductance (Ld)
Range:
Function:
Size
related
*
[0.0 -
1000.0
mH]
Enter line-to-common direct axis
inductance of the PM motor. Obtain the
value from the permanent magnet motor
datasheet.
If only line-line data is available, divide
the line-line value by 2 to achieve the
line-common (star point) value. Alterna-
tively, measure the value with an
inductance meter. This also takes the
inductance of the cable into account.
Divide the measured value by 2 and enter
the result.
This parameter is only active when
parameter 1-10 Motor Construction
is set to
[1] PM, non-salient SPM
(Permanent
Magnet Motor) or
[5] Sync. Reluctance
.
For a selection with 1 decimal, use this
parameter. For a selection with 3 decimals,
use
parameter 30-80 d-axis Inductance (Ld)
FC 302 only.
NOTICE
The parameter value is updated
after each torque calibration if
option
[3] 1st start with store
or
option
[4] Every start with store
is
selected in
.
1-38 q-axis Inductance (Lq)
Range:
Function:
Size related
*
[0.000 - 1000
mH]
Set the value of the q-axis
inductance. See the motor
datasheet.
1-39 Motor Poles
Range:
Function:
Size related
*
[2 - 132 ] Enter the number of motor poles. Make
sure not to enter pairs of motor poles.
Poles ~n
n
@ 50 Hz
~n
n
@ 60 Hz
2
2700–2880
3250–3460
4
1350–1450
1625–1730
6
700–960
840–1153
Table 3.6 Pole Number for Normal Speed Ranges
Parameter Descriptions
VLT
®
AutomationDrive FC 301/302
52
Danfoss A/S © 10/2018 All rights reserved.
MG33MP02
3
3