5-66 Terminal X30/6 Pulse Output Variable
Select the variable for readout on terminal X30/6.
This parameter is active when VLT
®
General Purpose I/O MCB 101
is installed in the frequency converter.
Same options and functions as
parameter group 5-6* Pulse
Outputs
.
Option:
Function:
[107] Speed
[108] Torque
[109] Max Out Freq
[119] Torque % lim
5-68 Pulse Output Max Freq #X30/6
Range:
Function:
Size
related
*
[0 -
110000
Hz]
NOTICE
This parameter cannot be adjusted
while the motor is running.
Select the maximum frequency on
terminal X30/6 referring to the output
variable in
.
This parameter is active when VLT
®
General Purpose I/O MCB 101 is installed
in the frequency converter.
3.6.7 5-7* 24 V Encoder Input
Connect the 24 V encoder to terminal 12 (24 V DC supply),
terminal 32 (channel A), terminal 33 (channel B), and
terminal 20 (GND). The digital inputs 32/33 are active for
encoder inputs when
[1] 24 V encoder
is selected in
parameter 1-02 Flux Motor Feedback Source
and
parameter 7-00 Speed PID Feedback Source
. The encoder
used is a dual-channel (A and B) 24 V type. Maximum
input frequency: 110 kHz.
Encoder connection to the frequency converter
24 V incremental encoder. Maximum cable length is 5 m
(16.4 ft).
130BA090.12
+24 V
DC
A
B
GND
13
12
18
37
32
27
19
29
33
20
24 V or 10–30 V encoder
Illustration 3.41 Encoder Connection
B
A
B
A
130BA646.10
CW
CCW
Illustration 3.42 Encoder Rotation Direction
5-70 Term 32/33 Pulses Per Revolution
Range:
Function:
1024
*
[ 1 - 16384 ] Set the resolution of the encoder
connected to terminal 32/33 in pulses per
revolution.
Parameter Descriptions
VLT
®
AutomationDrive FC 301/302
132
Danfoss A/S © 10/2018 All rights reserved.
MG33MP02
3
3