14-21 Automatic Restart Time
Range:
Function:
is set to
[1]–
[13] Automatic reset
.
14-22 Operation Mode
Option:
Function:
Use this parameter to specify normal operation;
to perform tests; or to initialize all parameters
except
,
, and
. This function is
active only when the power is cycled to the
frequency converter.
Select
[0] Normal operation
for normal operation
of the frequency converter with the motor in
the selected application.
Select
[1] Control card test
to test the analog
and digital inputs and outputs and the +10 V
control voltage. The test requires a test
connector with internal connections. Use the
following procedure for the control card test:
1.
Select
[1] Control card test
.
2.
Disconnect the mains supply and wait
for the indicator light in the display to
go out.
3.
Set switches S201 (A53) and S202
(A54) to ON/I.
4.
Insert the test plug (see
).
5.
Connect to mains supply.
6.
Carry out various tests.
7.
The results are shown on the LCP and
the frequency converter moves into an
infinite loop.
8.
Parameter 14-22 Operation Mode
is
automatically set to normal operation.
Carry out a power cycle to start up in
normal operation after a control card
test.
If the test is OK
LCP readout: Control card OK.
Disconnect the mains supply and remove the
test plug. The green indicator light on the
control card lights up.
If the test fails
LCP readout: Control card I/O failure.
Replace the frequency converter or control
card. The red indicator light on the control card
is turned on. Test plugs (connect the following
terminals to each other): 18 - 27 - 32; 19 - 29 -
33; 42 - 53 - 54
14-22 Operation Mode
Option:
Function:
130BA097.12
FC 302
FC 301
FC 301 &
FC 302
13
12
18
37
32
27
19
29
33 20
50
39 42
54
53
55
19
18
12 13
20
33
27
32
Illustration 3.63 Test Plugs
Select
[2] Initialisation
to reset all parameter
values to default settings, except for:
, and
. The frequency
converter resets during the next power-up.
Parameter 14-22 Operation Mode
also returns to
the default setting
[0] Normal operation
.
[0]
*
Normal
operation
[1] Control
card test
Remember to set switches S201 (A53) and S202
(A54) as specified in the parameter description
when performing a control card test. Otherwise,
the test fails.
[2] Initiali-
sation
Select this option to perform initialization. This
option does not clear the service logs.
[3] Boot mode
[5] Clear
service
logs
NOTICE
Save the log information using MCT 10
Set-up Software before clearing the
service logs.
Select this option and perform a power cycle to
clear the log. For more information, see
chapter 3.15.4 Clearing the Service Log
. See also
parameter 16-42 Service Log Counter
.
14-24 Trip Delay at Current Limit
Range:
Function:
60 s
*
[0 -
60 s]
Enter the current limit trip delay in s. When the
output current reaches the current limit
(
), a warning is
triggered. When the current limit warning has
been continuously present for the period specified
in this parameter, the frequency converter trips. To
run continuously in current limit without tripping,
Parameter Descriptions
Programming Guide
MG33MP02
Danfoss A/S © 10/2018 All rights reserved.
195
3
3