8-02 Control Word Source
Select the source of the control word: 1 of 2 serial interfaces or 4
installed options. During initial power-up, the frequency
converter automatically sets this parameter to
[3] Option A
if it
detects a valid fieldbus option installed in slot A. When the
option is removed, the frequency converter detects a configu-
ration change, sets
parameter 8-02 Control Word Source
to default
setting
[1] FC RS485
, and trips. If an option is installed after initial
power-up, the setting of
parameter 8-02 Control Word Source
does
not change, but the frequency converter trips and shows:
Alarm
67, Option Changed
.
When retrofitting a bus option into a frequency converter that
did not have a bus option installed earlier, change the control to
bus-based. This change is required for safety reasons to avoid an
unintended change.
Option:
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
[0]
None
[1]
FC RS485
[2]
FC USB
[3]
Option A
[4]
Option B
[5]
Option C0
[6]
Option C1
[30] External Can
8-03 Control Word Timeout Time
Range:
Function:
1 s
*
[ 0.1 -
18000 s]
Enter the maximum time expected to pass
between the reception of 2 consecutive
telegrams. If this time is exceeded, it indicates
that the serial communication has stopped. The
function selected in
is then carried out. A valid
control word triggers the timeout counter.
8-04 Control Word Timeout Function
Select the timeout function. The timeout function activates when
the control word fails to be updated within the time period
specified in
parameter 8-03 Control Word Timeout Time
Option:
Function:
NOTICE
To change the set-up after a timeout,
configure as follows:
1.
Set
to
[9] Multi set-up
.
2.
Select the relevant link in
parameter 0-12 This Set-up
Linked to
.
8-04 Control Word Timeout Function
Select the timeout function. The timeout function activates when
the control word fails to be updated within the time period
specified in
parameter 8-03 Control Word Timeout Time
Option:
Function:
[0]
Off
Resumes control via fieldbus (fieldbus or
standard), using the most recent control word.
[1]
Freeze
output
Freezes output frequency until communication
resumes.
[2]
Stop
Stops with auto restart when communication
resumes.
[3]
Jogging
Runs the motor at jog frequency until
communication resumes.
[4]
Max. speed Runs the motor at maximum frequency until
communication resumes.
[5]
Stop and
trip
Stops the motor, then resets the frequency
converter to restart:
•
Via the fieldbus.
•
Via [Reset].
•
Via a digital input.
[6]
Qstop and
trip
NOTICE
This option is available only with
software version 48.XX.
Stops the motor with the quick stop ramp
(
parameter 3-81 Quick Stop Ramp Time
). Perform
a reset to restart the frequency converter.
[7]
Select
setup 1
Changes the set-up after a control word
timeout. If communication resumes after a
timeout,
either resumes the set-up used before
the timeout, or retains the set-up endorsed by
the timeout function.
[8]
Select
setup 2
See
[7] Select set-up 1
.
[9]
Select
setup 3
See
[7] Select set-up 1
.
[10] Select
setup 4
See
[7] Select set-up 1
.
[26] Trip
Parameter Descriptions
VLT
®
AutomationDrive FC 301/302
154
Danfoss A/S © 10/2018 All rights reserved.
MG33MP02
3
3