![CTI 2500-C100 Скачать руководство пользователя страница 97](http://html1.mh-extra.com/html/cti/2500-c100/2500-c100_nstallation-and-operation-manual_2693825097.webp)
CTI 2500 Installation and Operation Guide V2.8
97
STW 232:
STW 238
Profibus I/O Slave Diagnostic Status
The corresponding bit will be set to 1 if the slave signals a diagnostic that has
not been read by a RSD RLL instruction.
The least significant bit (16) of STW 232 corresponds to Slave #`1. See table
below.
Word
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
232
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
233
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
234
48
47
46
45
44
43
42
41
40
39
38
37
36
35
34
33
235
64
63
62
61
60
59
58
57
56
55
54
53
52
51
50
49
236
80
79
78
77
76
75
74
73
72
71
70
69
68
67
66
65
237
96
95
94
93
92
91
90
89
88
87
86
85
84
83
82
81
238
112
111
110
109
108
107
106
105
104
103
102
101
100
99
98
97
STW 239:
STW 240
Source SF Program/SF Subroutine Checksum
STW 241:
STW 242
Compiled SF Program/SF Subroutine Checksum
STW 243
Reserved
STW 244
Additional Controller Status Flags
Bit 1
Controller Mode (0 = Program Mode, 1 = Run mode)
Bit 2
Scan Type (0 = Variable, 1 = Fixed)
Bit 3
User Program Source (0 = RAM, 1 = Flash)
Bit 4
Ethernet Port Link Status (1= Connected)
Bit 5
TCP/IP Network Status (1 = TCP/IP Stack is Operational)
Bit 6
Duplicate IP Address Status (1 = Duplicate Detected)
Bit 7 - 16
Reserved
STW 245
Additional Controller Error Status
Bit 1
Fatal Error Flag (1 = Fatal Error Present).
Bit 2
Reserved
Bit 3
Remote I/O Base Failure (1 = One or more bases are not communicating)
A base that is configured and enabled cannot be logged in.
Bit 4 - 16
Reserved
STW 246
Fatal Error Code
Contains the fatal error code when a fatal error is present
STW 247-
STW 257
CTI Support Diagnostics
Subject to change
STW 258-
STW 259
Product Serial Number
Contains the serial number of the controller stored as a 32 bit value
STW260
Firmware Major Release Number
STW 261
Firmware Minor Release Number
STW 262-
STW 298
CTI Support Diagnostics
Subject to change
STW 299
Peak Scan Time
16 bit representation
STW300
Normal Io Last Scan (msec)
STW301
N
ormal Io Peak Scan (msec)
STW302
Profibus Last Scan (msec)
STW303
Profibus Peak Scan (msec)
STW304
Main RLL Last Scan (msec)
STW305
Main RLL Peak Scan (msec)
STW306
Special Function Io Last Scan (msec)
STW307
Special Function Io Peak Scan (msec)
Содержание 2500-C100
Страница 1: ...CTI 2500 Series Controller INSTALLATION AND OPERATION GUIDE Version 2 8 CTI Part 062 00370 2500IOG...
Страница 10: ......
Страница 30: ......
Страница 34: ......
Страница 42: ......
Страница 50: ......
Страница 56: ......
Страница 62: ......
Страница 84: ......
Страница 102: ......
Страница 106: ......
Страница 110: ......