CTI 2500 Installation and Operation Guide V2.8
79
Status Code
Status
U15
Writing the downloaded bootloader to flash memory
U16
Searching for an IO Interface firmware image in flash memory
U17
Validating the IO Interface firmware image found in flash memory
U18
Copying the IO Interface firmware image from flash memory to DRAM and validating
copy
U19
Writing the IO Interface firmware image to the I/O processor flash memory
U20
Checking the Image File in flash memory to see if it is used for manufacturing
purposes only
U21
Checking to see if a Profibus upgrade is needed (based upon CPU hardware)
U22
Searching for a Profibus Application Image in the Image File saved in flash memory
U23
Searching for a Profibus Loader Image in the Image File saved in flash memory
U24
Validating the Profibus Application Image found in flash memory
U25
Validating the Profibus Loader Image found in flash memory
U26
Copying the Profibus Application Image from flash memory to DRAM and validating
copy
U27
Copying the Profibus Loader Image from flash memory to DRAM and validating copy
U28
Writing the Profibus Application to the Profibus processor flash memory
U36
Searching for Profibus FPGA image in flash memory
U37
Validating Profibus FPGA image found in flash memory
U38
Copying Profibus FPGA image from flash memory to DRAM and validating copy
U39
Writing Profibus FPGA configuration and boot code to FPGA flash
10.5 Firmware Update Errors
If an error occurs during the firmware update procedure, the procedure will stop and wait for
corrective action. An error code will be displayed on the MSD. The following table describes the
error codes and the corrective action.
Error Code Description
Corrective Action
E16
Firmware update failed
Rerun the firmware update procedure. If the error
persists, contact CTI.
E17
Unable to write the firmware
update status flag.
Rerun the firmware update procedure. If the error
persists, contact CTI.
E18 – E25
Unable to locate or execute the
main firmware file loader
Contact CTI.
E26
An error was encountered when
attempting to open the SD card
file
Reformat the SD card, copy the firmware file to
the SD card, and rerun the firmware update
procedure.
E27
The firmware update file could not
be read
Delete the firmware update file, re-copy the
firmware update to the SD card, and rerun the
firmware update procedure. If the error persists,
try using a new SD card for the firmware update.
E28
The SD card directory could not
be read
Reformat the SD card, copy the firmware update
file to the SD card, and rerun the firmware update
procedure.
E29
No firmware update (.plc) file
could be found on the SD card or
more than one firmware update
file was found.
One and only one firmware update file is allowed
on the SD card. This file must be in the root
directory. Take the necessary action to ensure
that the desired firmware update file (and only the
file), is located in the root directory. Once this has
been done, rerun the firmware update procedure.
Содержание 2500-C100
Страница 1: ...CTI 2500 Series Controller INSTALLATION AND OPERATION GUIDE Version 2 8 CTI Part 062 00370 2500IOG...
Страница 10: ......
Страница 30: ......
Страница 34: ......
Страница 42: ......
Страница 50: ......
Страница 56: ......
Страница 62: ......
Страница 84: ......
Страница 102: ......
Страница 106: ......
Страница 110: ......