Jumper
Use
Open
Closed
Comments
Switch
Off
On
A or 1
Selects whether the
controller reports
SIMATIC 505 model-
equivalent memory
capacity or APT
Expanded Memory
capacity when queried
by task code 6D.
SIMATIC 505
Model
Equivalent
Memory
APT
Expanded
Memory
See Note 1
below
APT Expanded Memory Mode will not
work properly with legacy 505 Workshop
versions.
Changes to APT files are required to use
the larger APT Expanded Memory and
additional control relays.. Contact CTI.
B or 2
Selects the Serial Port
function.
The serial
port functions
as a
programming
port
The serial
port
functions as
a printer port
When the serial port is selected as a
“Printer Port” it will not respond to task
code or other requests. It is output only.
C or 3
Ethernet Port
Auto-Crossover Enable
Auto-
Crossover is
Disabled. The
port uses MDI
mode
Auto-
Crossover is
enabled
The Ethernet port operates most reliably
in MDI mode. In MDI mode the port can
connect to switches and hubs using a
standard straight-thru cable and all other
devices that support that support auto-
crossover capability. Auto-crossover
should be enabled on the processor
Ethernet port only in exceptional cases.
D or 4
Used to clear all IP
Parameters (IP
address, subnet mask,
and default
router/gateway.
(See Section 7.4.3)
No action
Clears the IP
parameters
during power
up start.
After clearing the IP Parameters, placing
the jumper in the Open position and re-
powering the controller will automatically
generate a temporary link local address,
which can be used to set a permanent
static address.
E or 5
Reserved
Jumpers should be in the Open position
Auxiliary switches be in the Off position
F or 6
Reserved
Note 1:
Model C400 controllers with firmware version 8.01 and above will also report additional control
relays (C32769 – C56320) when Jumper A is closed.
Содержание 2500-C100
Страница 1: ...CTI 2500 Series Controller INSTALLATION AND OPERATION GUIDE Version 2 8 CTI Part 062 00370 2500IOG...
Страница 10: ......
Страница 30: ......
Страница 34: ......
Страница 42: ......
Страница 50: ......
Страница 56: ......
Страница 62: ......
Страница 84: ......
Страница 102: ......
Страница 106: ......
Страница 110: ......