CTI 2500 Installation and Operation Guide V2.8
92
STW 3 -
STW 9
Status of DP channel slaves
.
Set to 0 if slave is online, configured, and enabled. The least significant bit (16)
of Word 3 corresponds to Slave #1. See the table below.
Word
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
3
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
4
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
5
48
47
46
45
44
43
42
41
40
39
38
37
36
35
34
33
6
64
63
62
61
60
59
58
57
56
55
54
53
52
51
50
49
7
80
79
78
77
76
75
74
73
72
71
70
69
68
67
66
65
8
96
95
94
93
92
91
90
89
88
87
86
85
84
83
82
81
9
112
111
110
109
108
107
106
105
104
103
102
101
100
99
98
97
STW 10
Dynamic Scan Time
Scan time of the previous scan.
STW 11:
STW 26
I/O Module Status
STW 11 represents the local base
STW 12 – 26 represent remote bases 1 – 15.
For all words, the most significant bit (1) represents slot 16 and the least
significant bit (16) represents slot 1 as shown below.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
A bit is set to 0 if the module status is good. It is set to 1 if any of the following
conditions is true:
•
Installed module does not match configuration for the slot
•
The slot is configured but no module is installed in the slot.
•
The slot is not configured but a module is installed.
•
Module fail is asserted and module fail bit is set
STW 27:
STW 138
Profibus RBC Module Status
.
Provides module status for modules in a 505 base using a Profibus RBC.
Status Word 27 corresponds to Profibus RBC slave # 1. Subsequent words
correspond to Slave # 2, Slave # 3, etc.
For all words, the most significant bit represents slot 16 and the least significant
bit (16) represents slot 1 as shown below.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
A bit is set to 0 if the module status is good. It is set to 1 if any of the following
conditions is true:
•
Installed module does not match configuration for the slot
•
The slot is configured but no module is installed in the slot.
•
The slot is not configured but a module is installed.
STW 139
Number of Forced Bits.
Current count of forced X, Y, and C.
STW 140
Number of Forced Words
Current count of forced WX and WY.
Содержание 2500-C100
Страница 1: ...CTI 2500 Series Controller INSTALLATION AND OPERATION GUIDE Version 2 8 CTI Part 062 00370 2500IOG...
Страница 10: ......
Страница 30: ......
Страница 34: ......
Страница 42: ......
Страница 50: ......
Страница 56: ......
Страница 62: ......
Страница 84: ......
Страница 102: ......
Страница 106: ......
Страница 110: ......