![CTI 2500-C100 Скачать руководство пользователя страница 29](http://html1.mh-extra.com/html/cti/2500-c100/2500-c100_nstallation-and-operation-manual_2693825029.webp)
CTI 2500 Installation and Operation Guide V2.8
29
2.7 Setting the Controller IP Parameters
Using the Serial or USB Port
When connected to the serial or USB port, you can set the IP address and other IP parameters
using PLC Workshop (V4.11 or greater) or IPSET, a standalone utility that you can download
from the CTI web site.
Using the Ethernet Port
Firmware version 8.02 and above allows you to set the IP address and other IP parameters
when connected to the Ethernet port. To enable this capability, SW11 must be set to the closed
position. You can change the parameters using PLC Workshop (V4.11 or greater) or by
accessing the 2500 controller embedded web server with your PC web browser.
2.8 Automatic IP Address Assignment
The 2500 controller is shipped from CTI with the IP parameters cleared. After you power up the
controller, the IP address will be displayed as 0.0.0.0. When you connect the Ethernet port to a
switch or PC, the controller will automatically generate a temporary IP address. You can
connect to this address to set a permanent IP address. The address will be selected from a
range of “Link-Local” addresses reserved for this purpose (169.254.1.0 to 169.254.254.255)
with a subnet mask of 255.255.0.0 (/16).
NOTE:
The link-local address range is automatically used by Microsoft Windows when an IP Address cannot be
automatically obtained from the network DHCP server.
You can use Windows Control Panel to set your PC to a static address that is compatible with
the selected address. A compatible address:
•
Is within the Link-Local Range above,
•
Is not the same as the PLC IP address (displayed on the MSD),
•
Uses the same subnet mask (255.255.0.0)
Alternately, if your PC is using DHCP to obtain an IP address, you can automatically connect
using the following method:
1. Connect an Ethernet cable from the PC to the 2500 controller Ethernet port.
2. Reboot the PC.
NOTE
Depending on the PC configuration, it may take several minutes before the PC stops attempting to
contact a DHCP server and generates the link-local address. You can confirm when this is done by
opening the Command Prompt box and typing IPCONFIG.
Содержание 2500-C100
Страница 1: ...CTI 2500 Series Controller INSTALLATION AND OPERATION GUIDE Version 2 8 CTI Part 062 00370 2500IOG...
Страница 10: ......
Страница 30: ......
Страница 34: ......
Страница 42: ......
Страница 50: ......
Страница 56: ......
Страница 62: ......
Страница 84: ......
Страница 102: ......
Страница 106: ......
Страница 110: ......