CTI 2500 Installation and Operation Guide V2.8
96
STW 211:
STW 217
Profibus Poll Enable Flags
The corresponding bit is set to 1 when the slave is defined and enabled for
polling. The least significant bit (16) of STW 211 corresponds to Slave #1. See
table below.
Word
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
211
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
212
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
213
48
47
46
45
44
43
42
41
40
39
38
37
36
35
34
33
214
64
63
62
61
60
59
58
57
56
55
54
53
52
51
50
49
215
80
79
78
77
76
75
74
73
72
71
70
69
68
67
66
65
216
96
95
94
93
92
91
90
89
88
87
86
85
84
83
82
81
217
112
111
110
109
108
107
106
105
104
103
102
101
100
99
98
97
STW 218
Unused
STW 219
RLL Task Overrun
The bit corresponding to the RLL task is set if the RLL task does not complete
in the user specified cycle time. The most significant bit (bit 1) corresponds to
RLL Task 1.
STW 220:
STW 222
Unused
STW 223
STW 224
Binary Time of Day
Contains the relative millisecond of the current day expressed as a 32 bit
unsigned integer.
STW 225
Binary Relative Day
Contains the relative day, with January 1, 1984 being day 0.
STW 226
Time of Day Status
Bit 1
1 = Current time is prior to time reported in the last Task 1 RLL scan
Bit 2 – 9
Reserved
Bit 10
1 = Time is Valid (has been Set)
Bit 11
Unused
Bit 12 - 13
Time Resolution
00 = Time Resolution is .001 second
01 = Time Resolution is .01 second
02 = Time Resolution is 0.1 second
03 = Time Resolution is 1 second
Bit 14 - 16
Reserved
STW 227:
STW 228
Unused
STW 229:
STW 230
Unused
STW 231
Profibus I/O Status
Bit 1
1 = DP in Operate State – inputs available, outputs driven
Bit 2
1 = DP in Clear State – Inputs available
Bit 3
1 = Error: Unable to download configuration to Profibus interface
Bit 4
1 = Error: Unable to retrieve slave diagnostic data from Profibus interface
Bit 5
1 = Error: DP bus error
Bit 6
1 = One or more DP slaves expected to be in data exchange mode are not
operational.
Bit 7 – 15
Unused.
Bit 16
1= DP Bus has not been configured and activated
Содержание 2500-C100
Страница 1: ...CTI 2500 Series Controller INSTALLATION AND OPERATION GUIDE Version 2 8 CTI Part 062 00370 2500IOG...
Страница 10: ......
Страница 30: ......
Страница 34: ......
Страница 42: ......
Страница 50: ......
Страница 56: ......
Страница 62: ......
Страница 84: ......
Страница 102: ......
Страница 106: ......
Страница 110: ......