![CTI 2500-C100 Скачать руководство пользователя страница 68](http://html1.mh-extra.com/html/cti/2500-c100/2500-c100_nstallation-and-operation-manual_2693825068.webp)
CTI 2500 Installation and Operation Guide V2.8
68
Code
Description
Correction
0400
Diagnostic Error
Indicates that a general diagnostic error
has occurred.
Error details can be obtained from the system
event log.
0600
Hardware Failure
Indicates that a failure in a hardware
component has been detected.
Error details can be obtained from the system
event log.
0608
System Clock Failure.
Indicates the system clock cannot be
accessed.
To clear this error you must cycle power to the
controller. If the problem persists, contact CTI
Product Support.
060b
L Memory Invalid: Power loss during in-
progress RLL edit operation.
After clearing this error, you must reload the RLL.
060C
L Memory Invalid: Power loss during L
memory resize operation
After clearing this error, you must reload the RLL.
060d
S Memory Invalid: Power loss during in-
progress S memory edit operation.
After clearing this error, you must reload the RLL.
060F
System service failure.
To clear this error, you must cycle power to the
controller. If the problem persists, contact CTI
Product Support.
0611
RLL Source checksum error detected
during power-up start.
Indicates that the RLL is invalid and
cannot be compiled.
After clearing the fatal error using Partial or
Complete Restart, you must reload the RLL
Program to prevent this error from re-occurring.
0612
S Memory checksum error detected
during power-up start.
Indicates the Special Function source is
invalid and cannot be compiled.
After clearing the fatal error using Partial or
Complete Restart, you must reload the User
Program to prevent this error from re-occurring.
0615
Startup RLL compile failed
Indicates the RLL failed to compile
during a power-on start
Error details can be obtained from the system
event log.
After clearing the fatal error using Partial or
Complete Restart, you will need to correct RLL
errors before it will compile.
0616
Startup SFP/SFS compile failed
Indicates at least one SFP or SFS failed
to compile during a power-on start.
Error details can be obtained from the system
event log.
After clearing the fatal error using Partial or
Complete Restart, you will need to correct the
SFP or SFS error and re-enable the program or
subroutine.
0618
I/O Interface Timeout
Indicates the I/O interface failed to
respond to a request from the main
processor.
Clear the error using Partial or Complete Restart.
If this error persists, contact CTI Product Support.
0620
Profibus I/O Error
Indicates that the Profibus interface
experienced a fatal error.
Error details can by obtained from the system
event log.
Clear the error using Partial or Complete restart.
If the action above does not clear the error,
remove the battery and cycle power.
If the error persists, contact CTI Product Support.
0700
Control block data is invalid
These errors indicate that memory has been
corrupted or that a problem exists in the OS
firmware.
0701
Expression evaluation failed due to
corrupt or invalid expression
0702
SF Execution failed--Program
Содержание 2500-C100
Страница 1: ...CTI 2500 Series Controller INSTALLATION AND OPERATION GUIDE Version 2 8 CTI Part 062 00370 2500IOG...
Страница 10: ......
Страница 30: ......
Страница 34: ......
Страница 42: ......
Страница 50: ......
Страница 56: ......
Страница 62: ......
Страница 84: ......
Страница 102: ......
Страница 106: ......
Страница 110: ......