![CTI 2500-C100 Скачать руководство пользователя страница 88](http://html1.mh-extra.com/html/cti/2500-c100/2500-c100_nstallation-and-operation-manual_2693825088.webp)
CTI 2500 Installation and Operation Guide V2.8
88
Code
Description
Correction
0620
Profibus I/O Error
Indicates that the Profibus interface
experienced a fatal error.
Error details can be obtained from the system
event log.
Clear the error using Partial or Complete restart.
If the action above does not clear the error,
remove the battery and cycle power.
If the error persists, contact CTI product support.
0700
Control block data is invalid
These errors indicate that memory has been
corrupted or that a problem exists in the OS
firmware.
After clearing the error using Partial or Complete
Restart, try reloading the program. If the error
persists, contact CTI product support.
0701
Expression evaluation failed due to
corrupt or invalid expression
0702
SF Execution failed--Program
evaluation data is invalid
0703
Expression evaluation failed due to
corrupt or invalid parameter
0704
SF number from RLL is invalid
Task Code Errors
To aid in diagnosing errors, the following table provides a list of all task code error codes
returned in a task code 00 error reply.
Error Code
(Hexadecimal)
Description
01
Reset Current Transaction
02
Address out of Range (other than ladder logic)
03
Requested data not found
04
Illegal Task Code Request
05
Request exceeds available memory
06
Diagnostic fail on power up
07
Fatal error detected
08
Keylock/password protection error
09
Incorrect amount of data sent with request
0A
Illegal request in current operational mode
0B
Network was not deleted
0C
Attempted write operation did not verify
0D
Illegal number of ASCII characters received
0E
Illegal request when running from EEPROM or flash
0F
Data not inserted
10
Data not written
11
Illegal data sent with command
12
Invalid operation with NIM local/remote mode (obsolete)
13
The store and forward buffer is busy
14
No response from special function module
15
Illegal instruction found in program memory (may include memory
address)
16
Attempted to write to protected variable (e.g. TCC, TCP)
17
No response from PLC (e.g. single scan not performed)
Содержание 2500-C100
Страница 1: ...CTI 2500 Series Controller INSTALLATION AND OPERATION GUIDE Version 2 8 CTI Part 062 00370 2500IOG...
Страница 10: ......
Страница 30: ......
Страница 34: ......
Страница 42: ......
Страница 50: ......
Страница 56: ......
Страница 62: ......
Страница 84: ......
Страница 102: ......
Страница 106: ......
Страница 110: ......