CTI 2500 Installation and Operation Guide V2.8
76
8. Start the file download by pressing ‘Send’. HyperTerminal displays a window showing
the status of the file transfer. Once the transfer is initiated, the MSD should display “U02”
Once the transfer has completed successfully, the MSD should display “U06”, indicating the
controller is starting to write the new firmware to flash memory. The decimal points will flash
in sequence to indicate progress.
CAUTION:
While the flash is being updated, do NOT remove power. This will result in incomplete or missing
firmware components, making the controller inoperable.
Should you inadvertently lose power, rerunning the firmware update procedure and successfully
completing it will allow you to use the controller in most cases.
During the update, the MSD will cycle through other update numbers as the firmware
components are written to the flash. When the flash update has completed successfully, the
MSD will display U00, indicating the flash has been successfully written.
9. Disconnect power from the base and remove the controller from the base.
10. Set the firmware update switch to the Normal position. See Section 2.3. Reinstall the
controller in the base and apply power. The controller should start up in normal operating
mode.
Содержание 2500-C100
Страница 1: ...CTI 2500 Series Controller INSTALLATION AND OPERATION GUIDE Version 2 8 CTI Part 062 00370 2500IOG...
Страница 10: ......
Страница 30: ......
Страница 34: ......
Страница 42: ......
Страница 50: ......
Страница 56: ......
Страница 62: ......
Страница 84: ......
Страница 102: ......
Страница 106: ......
Страница 110: ......