Table of Functions
232
GM2 Series VFD
890054-00-00
Code
Comm.
Address
Name
Setting Range
Initial
Value
Property*
V/F
SL
Ref.
AP.32
1
0h1820
PID output
scale
0.1
–1000.0 (%)
100
X
O
O
AP.33
1
0h181F
PID output
inverse
0
No
0: No
X
O
O
1
Yes
AP.34
1
0h1822
Pre-PID
Frequency
0.00
–Maximum
frequency (Hz)
0
X
O
O
AP.35
1
0h1823
Pre-PID Exit
Level
0.0
–100.0 (%)
0
X
O
O
AP.36
1
0h1824
Pre-PID delay
time
0
–9999 (s)
600
O
O
O
AP.37
1
0h1825
PID sleep
mode delay
time
0.0
–999.9 (s)
60
O
O
O
AP.38
1
0h1826
PID sleep
mode
frequency
0.00
–Maximum
frequency (Hz)
0
O
O
O
AP.39
1
0h1827
PID wake-up
level
0
–100 (%)
35
O
O
O
AP.40
1
0h1828
PID wake-up
mode setting
0
Below
Level
0: Below
Level
O
O
O
1
Above
Level
2
Beyond
Level
AP.43
1
0h182B
PID unit gain
0.00
–300.00 (%)
100
O
O
O
AP.44
1
0h182C
PID unit scale
0
x100
2: x 1
O
O
O
1
x10
2
x 1
3
x 0.1
4
x 0.01
AP.45
1
0h182D
PID 2nd
proportional
gain
0.0
–1000.0 (%)
100
X
O
O
[1] Displayed when AP.01 is set to 2 (Proc PID).
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Страница 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...