19
GM2 Series VFD
890054-00-00
Installing the Inverter
•
Power supply cables must be connected to the R, S, and T terminals and output wiring to the motor
must be connected to the U, V, and W terminals. Opposite connections may damage the product.
•
Power Terminals (R/S/T, U/V/W and B1/B2) provide a Screw Clamp type connection. It is recommended
to use a Ring type terminal to meet UL connection requirements eventhough the terminals will accept
Spade, Slotted Ring, Ferrule and bare wire connections,
•
The inverter’s power terminal connections c
an cause harmonics that may interfere with other
communication devices located near to the inverter. To reduce interference the installation of noise
filters or line filters may be required.
•
Are power factor correction capacitors, surge protection and electromagnetic interference filters
installed correctly?
•
If a contactor is installed on the output side of the inverter (motor side), do not operate the contactor in
conjunction with the inverter start/stop control.
•
Metal debris in the inverter may cause inverter failure.
Step 4 Control Terminal Wiring
The illustrations below show the detailed layout of control wiring terminals, and control board
switches. Ensure that the cables selected meet or exceed the specifications in 1.5
Control Board Switches
Switch
Description
SW1
NPN/PNP mode selection switch
SW2
Terminating Resistor selection switch
Connector
Name
Description
RJ-45 Connector
Connect to Remote Keypad, Smart Copier or connection for
RS-485 communication.
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Страница 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...