Learning Protection Features
172
GM2 Series VFD
890054-00-00
Low Voltage Fault
When the internal DC link voltage drops due to a power loss, the inverter turns off the
output and a low voltage fault
(Lut)
occurs after the delay time set in Pr.81 (Low voltage
fault delay time). When the voltage recovers, the fault clears and the inverter is ready to
resume operation. Eith
er Relay1 or Relay2 (OU.31 or OU.33) can be set to 11 (Low Voltage) to
provide an output signal.
Group Code
Name
Setting
Setting Range
Unit
Pr
81
Low voltage trip
decision delay time
0.0
0
–
60
sec
OU
31
Multi-function (digital)
relay 1 item
11 Low Voltage
-
-
33
Multi-function (digital)
relay 2 item
Low Voltage Fault Setting Details
Code and
Features
Description
Pr.81 LVT Delay
When a low voltage condition occurs, the inverter blocks it output. A
relay, if set to 11 (Low Voltage) will change state immediately. Then,
after the delay time, the inverter generates a low voltage fault (Lut). The
LVT Delay time does not apply to the relay outputs.
Output Block by Multi-function (digital) Terminal
Set one
of the digital input terminals (P1 ~ P5) to 5 (BX). When activated (
bx
on display),
the inverter response is determined by Pr.45 (Bx Trip Mode). Set to (0) coast to a stop, Set
to (1) decelerate to a stop.
Group Code
Name
Setting
Setting Range
Unit
In
65~69
Px terminal setting
options
5
BX
-
-
Pr
45
Bx Trip Mode
0
Coast
0 - 1
-
1
Dec
Output Block by Multi-function (digital) Terminal Setting Details
Code and
Features
Description
In.65~69 Px
Define
When a digital input terminal is set to 5 (BX) and is activated during
operation,
the inverter response is determined by Pr.45 (Bx Trip
Mode).
0: Coast
→
The motor coasts to a stop
1: Decelerate
→
The motor decelerates to a stop.
While
‘
bx
’ is displayed
,
the inverter’s operati
ng information (frequency
and current) at the time of BX signal can be monitored. The inverter
resumes operation when the BX terminal is de-activated provided that
the Start/Run command is still active.
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Страница 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...