Learning Advanced Features
890054-00-00
GM2 Series VFD
133
Operational Noise Settings (Carrier Frequency
Settings)
Group Code
Name
Setting Range
Unit
Cn
04
Carrier Frequency
1.0HP~5.0HP
(0.75W~4.0kW)
2.0~15.0
kHz
7.5HP~15HP
(5.5kW~11kW)
1.0~15.0
Operational Noise Setting Details
Code and
Features
Description
Cn.04 Carrier
Freq
Power transistors (IGBT) at the output of the inverter generate and
supply a high frequency switching voltage to the motor. This switching
speed is refered to as the carrier frequency. Adustment of the carrier
frequency affects motor operating noise. A higher carrier frequency
reduces operational noise. A lower carrier frequency increases
operational noise.
Refer to the table below for carrier frequency settings according to the load level, control mode,
and capacity.
Capacity
Heavy Duty
Normal Duty
Setting Range
Initial
Value
Setting Range
Initial
Value
V/F
S/L
V/F
S/L
Minimum Maximum Minimum Maximum
Minimu
m
Maximu
m
Minimu
m
Maximu
m
1.0HP~5.0HP
(0.75kW~4.0
kW)
2
15
2
15
3
2
5
2
5
2
7.5HP~15HP
(5.5~11kW)
1
15
2
15
1
5
2
5
Note
Higher carrier frequency settings require derating of the output current of the
inverter. For derating specifications, refer to 11.6
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Страница 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...