Learning Advanced Features
98
890054-00-00
GM2 Series VFD
Jog Operation
The jog operation allows for a temporary control of the inverter. There are two was to apply a jog
and start command using the multi-function (digital) input terminals.
•
Jog-1 using a digital input terminal set to
JOG
along with a start command (Fx or Rx).
•
Jog-2 using a single digital input set to
FWD JOG
or
REV JOG.
Jog Operation 1-Forward
The jog operation is available in the forward (or reverse) direction, using two input terminals (Fx
and JOG). The table below lists parameter settings for a forward jog operation with a separate Run
(Fx) command.
Group Code
Name
Setting
Setting Range
Unit
dr
11 Jog frequency
10.00
0.50
–
Max Frequency
Hz
12
Jog run acceleration
time
20.00
0.00
–
600.00
sec
13
Jog run deceleration
time
30.00
0.00
–
600.00
sec
In
65
–
69
Px terminal setting
options
6 JOG
0
–
52
-
1 Fx
Forward Jog Description Details
Code and
Features
Description
In.65~69 Px Define
Select 6 (JOG) function from In.65 ~ 69 for one of the inputs.
[Terminal settings for jog operation]
dr.11 JOG Frequency Set the operating frequency.
dr.12 JOG Acc Time Set the acceleration speed.
dr.13 JOG Dec Time Set the deceleration speed.
If a signal is applied to the jog terminal while running (FX applied), the operating frequency
changes to the jog frequency.
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Страница 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...