Learning Protection Features
GM2 Series VFD
165
890054-00-00
Reference frequency Loss Setting Details
Code and
Features
Description
Pr.12 Lost Cmd
Mode
The inverter responds to the Speed Reference Loss based on
the setting of Pr.12 (Lost Command Mode).
Configuration
Function
0
None
The speed refernce becomes the operating
frequency without any protection function.
1
Free-Run
The inverter blocks output. The motor coasts to a
stop.
2
Dec
The motor decelerates and stops based on the
time set at Pr.07 (Trip Dec Time).
3
Hold
Input
The inverter calculates the average input value for
10 seconds before the loss of the speed reference
and uses it as the speed reference.
4
Hold
Output
The inverter calculates the average output
frequency for 10 seconds before the loss of the
speed reference and runs at that speed.
5
Lost
Preset
The inverter operates at the frequency set at Pr.14
(Lost Preset F).
Pr.15 AI Lost Level,
Pr.13 Lst Cmd Time
Configure the voltage level and time delay for speed
reference loss when using an analog input.
Configuration
Function
0
Half of
x1
Based on the values set at In.08 and In.12,
protective operation starts when the input signal
is reduced to half of the initial value of the analog
input set using the speed reference (Frq code in
Operations group) and it continues for the time
(speed loss decision time) set at Pr.13 (Lost Cmd
Time). For example, set the reference frequency to
2 (V1) at the Frq code, and In.06 (V1 Polarity) to 0
(Unipolar). When the voltage input drops to less
than half of the value set at In.08 (V1 Volt x 1), the
protective function is activated.
1
Below of
x1
The protective operation starts when the signal
becomes smaller than the initial value of the
analog input set by the speed reference and it
continues for the speed loss decision time set at
Pr.13 (Lost Cmd Time). Codes In.08 and In.12 are
used to set the standard values.
Pr.14 Lost Preset F
To run at a fixed speed, set the operation mode Pr.12 (Lost
Cmd Mode) to 5 (Lost Preset). When the protection function
operates, this sets the frequency for continued operation.
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Страница 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...