Learning Protection Features
GM2 Series VFD
163
890054-00-00
External Trip Signal
Set one of the multi-function (digital) input terminals In.65 ~ In.69 to 4 (External Trip). When
activated, the inverter trips
(Ext)
and blocks the output. The five input terminals can be set
independently to activate when closed or opened (set as NO or NC).
Group Code
Name
Setting
Setting
Range
Unit
In
65
–
69
Px terminal setting
options
4
External Trip
-
-
87
Multi-function
(digital) input
terminal selection
-
bit
External Trip Signal Setting Details
Code and
Features
Description
In.87 DI NC/NO
Sel
Selects the type of input contact. When the bottom LED segment is on,
the input operates as Normally Open, close to trip. When the top LED
segment is on, the input operates as Normally Closed, open to trip. The
corresponding terminals for each bit are as follows:
Bit
5
4
3
2
1
Terminals P5 P4 P3 P2 P1