Learning Advanced Features
152
890054-00-00
GM2 Series VFD
Multi-function (digital) relay Terminal Delay Time Settings
Set On/Off delay times to adjust the relay operation time. The delay times set in OU.50 and
OU.51 will be applied to both Relay 1 and Relay 2 except when the relay function is set to
(29) Trip.
Group Code
Name
Setting
Setting
Range
Unit
OU
50
Multi-function (digital)
output On delay
0.00
0.00
–
100.00
sec
51
Multi-function (digital)
output Off delay
0.00
0.00
–
100.00
sec
52
Multi-function (digital)
output contact selection
00*
00
–
11
bit
*Displayed as
on the Keypad.
Output Relay - NC/NO Selection Details
Code and
Features
Description
OU.52 DO NC/NO
Sel
Each relay can be set to operate as Type A or Type B. Type A is de-
energized in its normal state. Type B is energized in its normal state.
By setting the relevant bit to 0, it will operate as Type A (the NO
contact is Open) or setting it to 1 will operate as Type B (the NO
contact is Closed). Shown below in the table are Relay 1 and Relay 2
settings starting from the right bit.
Items
Bit On Status
Bit Off Status
Keypad
** Displayed as
on the keypad.
Relay2 (bit 2), Relay1 (bit 1)
00**
A type (NO)
11
B type (NC)
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Страница 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...