Technical Specification
890054-00-00
268
GM2 Series VFD
Installation
Enable
•
Within 2 seconds of attaching the remote keypad, operation is now from the remote keypad.
•
NOTE: If the frequency reference source (parameter Frq) is set to (4) V0 potentiometer, the
frequency reference will instantly switch between the inverter keypad and the remote keypad
when attaching (and detaching). Be cautious of the potentiometer setting to prevent the
motor from running at an undesireable frequency.
•
If communication is not linked between the inverter and the remote keypad, "E.vEr" is
displayed on the 7-Seg of the remote keypad.
•
“r
-
UL” is displayed on
the inverter 7-Seg display
while upload is in progress. “d” is displayed
on the remote 7-Seg display. When complete, the message disappears and the default
screen is displayed.
•
If there is a communication error while uploading, a warning message saying "Fail" is
displayed for 3 seconds, and saving the parameters to the remote keypad failed.
•
While saving, a message saying “W
-
dL” is displayed on the inverter 7
-Seg display. "U" is
displayed on the 7-Seg display of the remote keypad. When complete, the message
disappears and the default screen is displayed. If parameter data was not previously saved in
the remote keypad, you cannot set the dr.91 parameter to 5 for down loading.
•
If there is a communication error with the remote keypad, a warning message saying "Fail" is
displayed for 3 seconds, and saving the parameters to the inverter failed.
•
If the parameter code version (dr.97, dr.98) or the inverter model is different (copying
parameters between 200V
⇄
400V products), the WErr warning is displayed for 5 seconds
and saving parameters to the inverter fails.
Remove the RJ45 terminal cover on the inverter I/O cover. Connect the remote keypad cable to
the I/O RJ45 connector.
Connect the other end of the cable to the remote keypad.
When the remote keypad is connected and power applied to the inverter, the inverter keypad
buttons and potentiometer are disabled. These functions are replaced by the buttons and
potentiometer on the remote keypad.
Up Loading parameters
: Set dr.91 parameter to 4 (Remote UpLoad) to copy the parameter
settings saved in the inverter to the remote keypad.
Down Loading parameters
: After connecting the remote keypad with saved parameters, set
dr.91 parameter to 5 (Remote DownLoad) to copy the parameter settings saved in the remote
keypad to the inverter.
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Страница 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...