Learning Basic Features
65
Lea
rni
890054-00-00
GM2 Series VFD
Power-on Run
The inverter can be set to start operating (output power to the motor) as soon as the inverter
powers up.
See caution below
. When Ad.10, Power-on Run is set to 1 (yes) and a run command
remains enabled, the inverter will start immediately upon power up. Parameter drv (command
source) must be set to 1 (Fx/Rx-1) or 2 (Fx/Rx-2) along with an active run command. If drv is set to
Keypad, Power On Run does not function.
Group Code
Name
Setting
Setting
Range
Unit
Operation drv Command Source
1, 2 Fx/Rx-1 or Fx/Rx-2
0
–
4
-
Ad
10 Start with power on 1
Yes
0
–
1
-
Note
•
Power On Run and Speed Search
- A fault may be triggered if the inverter starts
operation while the load is still rotating. With Power On Run enabled, the inverter will
begin its operation in a normal V/F pattern and accelerate the motor. To prevent faults,
set speed search CN-71, bit 4 to 1. The inverter will perform a speed search at the
beginning of the operation.
•
With Power On Run not enabled, if the inverter has a run command enabled upon
power up, it will not start. The digital input (Run command) must first be de-activated
and reapplied to begin operation.
Take caution - With Power On Run enabled and a Run command applied, the motor
will begin rotating as soon as the inverter powers up.
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Страница 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...