Jog Operation 2-Fwd/Rev Jog by Multi-function (digital)
Terminal
A terminal that is set for a forward or reverse jog also starts the inverter. The table below lists
parameter settings for a forward (or reverse) jog operation. A separate Run (Fx) command is not
required.
Group Code
Name
Setting
Setting Range
Unit
dr
11 Jog Frequency
10.00
0.50
–
Maximum
frequency
Hz
12
Jog run acceleration
time
20.00
0.00
–
600.00
sec
13
Jog run deceleration
time
30.00
0.00
–
600.00
sec
In
65
–
69
Px terminal setting
options
46 FWD JOG
0
–
52
-
47 REV JOG
NOTE:
The priorities for speed reference inputs and associated Acc/Dec times via digital inputs are
as follows:
Dwell
overrides
Jog
overrides
Up/Down
overrides
Fixed Speed inputs
overrides
Frq setting
.
If a different operation command is entered during a jog operation (other than dwell), it is ignored
and the operation maintains the jog frequency.