RS-485 Communication Features
890054-00-00
GM2 Series VFD
192
Compatible Common Area Parameter
The following are common area parameters compatible with GM2, SG, and GX inverters.
Comm.
Address
Parameter
Scale
Unit R/W
Assigned Content by Bit
0h0000
Inverter model
-
-
R
16: GM2
0h0001
Inverter capacity
-
-
R
0: 0.75kW, 1: 1.5kW, 2: 2.2kW,
4: 5.5kW, 5: 7.5kW,
6: 11kW,
256 : 0.4kW, 259: 4.0kW
0h0002
Inverter input voltage
-
-
R
0: 220 V level, 1: 440 V level
0h0003
Version
-
-
R
(E.g.) 0h0100: Version 1.00
(E.g.) 0h0101: Version 1.01
0h0004
Reserved
-
-
R/W -
0h0005
Target frequency
0.01
Hz
R/W -
0h0006
Operation command
(option)
-
-
R
B15
Reserved
B14
0: Keypad Freq
1: Keypad Torq
2-16 Terminal block multi-
step speed
17: Up, 18: Down
19: STEADY
22: V1, 24: V0, 25: I2
26: Reserved
27: Built-in 485
28: Communication option
30: JOG, 31: PID
B13
B12
B11
B10
B9
B8
0: Keypad
1: Fx/Rx-1
2: Fx/Rx-2
3: Built-in 485
4: Communication option
B7
B6
R/W
B5
Reserved
B4
Emergency stop
B3
W: Trip initialization (0
→
1)
R: Trip status
B2
Reverse operation (R)
B1
Forward operation (F)
B0
Stop (S)
0h0007
Acceleration time
0.1
sec
R/W -
0h0008
Deceleration time
0.1
sec
R/W -
0h0009
Output current
0.1
A
R
-
0h000A
Output frequency
0.01
Hz
R
-
0h000B
Output voltage
1
V
R
-
0h000C
DC link voltage
1
V
R
-
0h000D
Output power
0.1
kW
R
-
0h000E
Operation status
-
-
-
B15
Reserved
B14
1: Frequency command
source by communication
(built-in, option)
B13
1: Start command source by
communication (built-in,
option)
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Страница 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...