GM2 Series VFD
890054-00-00
Learning Basic Features
Free Run Stop
When the run command is removed, the inverter output turns off and the motor/load coasts to a
stop.
Group Code
Name
Setting
Setting Range
Unit
Ad
08 Stop Mode
2
Free-Run
0
–
4
-
Note: With high inertia loads,
the load’s inertia will cause the motor to
continue rotating.
The inverter does not control the motor during Free-Run.
Power Braking
Power Braking is applied during deceleration w
hen the inverter’s DC voltage rises above a specified
level due to motor regenerated energy. The inverter determines the optimum deceleration rate and
will adjust the deceleration time or will reaccelerating the motor. Power braking can be used when
short deceleration times are needed without brake resistors or when optimum deceleration is
needed without causing an over voltage fault.
Group Code
Name
Setting
Setting
Range
Unit
Ad
08
Stop Mode
4
Power Braking
0
–
4
-
•
To prevent overheating or damaging the motor, do not apply power braking to the
loads that require frequent deceleration.
•
Stall prevention and power braking only operate during deceleration.
•
Power braking takes priority over stall prevention. In other words, when both bit3 and
bit4 of Pr.50 (stall prevention and flux braking) are set, power braking will take
precedence and operate.
•
Note if deceleration time is too short or inertia of the load is too great, an overvoltage
fault stll may occur.
•
Note when power braking is used, the actual deceleration time can be longer than the
pre-set deceleration time.
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Страница 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...